Thermostat Control - Daikin FTXS20K2V1B Service Manual

Inverter pair wall mounted type ftxs/atxs-k series
Hide thumbs Also See for FTXS20K2V1B:
Table of Contents

Advertisement

Main Functions
1.7

Thermostat Control

Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Detail
Thermostat OFF Condition
Thermostat ON Conditions
Cooling/Dry
Heating
Refer to Temperature Control on page 18 for details.
24
The temperature difference is in the zone A.
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry: 10 minutes, Heating: 10 seconds)
Zone C
Zone C
–1.5˚C
Zone B
Zone B
Zone A
Zone A
Zone A
Zone A
Zone B
Zone B
1.0˚C
Zone C
Zone C
Room thermistor temperature – target temperature
ON
ON
Cooling : –0.5˚C
Dry : –0.5˚C
Cooling : –2.0˚C
Dry : –2.5 ~ –2.0˚C
OFF
OFF
Room thermistor temperature – target temperature
OFF
OFF
1.5˚C
0˚C
ON
ON
SiBE041134EB
(R22110)
(R22126)
Functions and Control