Inverter Analyzer Check - Daikin FTXS20K2V1B Service Manual

Inverter pair wall mounted type ftxs/atxs-k series
Hide thumbs Also See for FTXS20K2V1B:
Table of Contents

Advertisement

Check
5.7

Inverter Analyzer Check

Check No.15
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using
an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or
some other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to
judge the cause of trouble easily and securely. (Connect an inverter analyzer as a quasi-
compressor instead of compressor and check the output of the inverter)
Step 1
Step 2
98
Characteristics
Operation Method
Be sure to turn the power off.
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10
VDC or below before carrying out the service work.
(1) Remove the terminals from
the compressor.
Compressor
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on
the terminals), it is possible to connect wires available on site to the outdoor unit from output
side of PCB. (Do not connect them to the compressor at the same time, otherwise it may
result in incorrect detection.)
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Be careful not to let the terminals (U,V,W)
touch each other. Otherwise, high voltage
is applied.
SiBE041134EB
Inverter analyzer
(R22731)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents