■Mode
This mode specifies whether Remote PAUSE can be executed forcibly by a device other than the external device which
performed Remote STOP or Remote PAUSE. If forced execution is not allowed, Remote PAUSE can be executed only by the
external device which performed Remote STOP or Remote PAUSE.
Forced execution is used when the external device which performed the remote operation cannot execute Remote PAUSE
because of a problem with the device.
Item
Forced execution not allowed (Remote RUN cannot be executed when other device
executes Remote STOP or Remote PAUSE.)
Forced execution allowed (Remote RUN can be executed when other device
executes Remote STOP or Remote PAUSE.)
Response data
There is no response data for the Remote PAUSE command.
Communication example
Set mode to "Forced execution not allowed" when executing Remote PAUSE.
■When communicating data in ASCII code
(Request data)
1
0
0
3
0
0
0
31H 30H 30H 33H
30H 30H 30H 30H
■When communicating data in binary code
(Request data)
Mode
03H 10H 00H 00H 01H 00H

Remote latch clear

This command executes remote latch clear to the access destination module.
Before executing the remote latch clear, set the status of the access destination module to STOP.
While the access destination is stopped or paused remotely by request from another external device:
• The remote latch clear cannot be executed. Abnormal completion of the command will occur.
• Cancel the Remote STOP or Remote PAUSE before executing the command.
Request data
■When communicating data in ASCII code
4 bytes
4 bytes
Subcommand
1
0
0
5
31H
30H
30H
35H
30H
30H 30H 30H
Mode
0
0
0
0
1
30H 30H 30H 31H
4 bytes
0
0
0
0
30H
30H
30H
30H
Mode
ASCII code
0
0
0
1
30H
30H
30H
31H
0
0
0
3
30H
30H
30H
33H
Binary code
01H 00H
03H 00H
4 COMMANDS
83
4.3 Remote Control