■When word device memory is read or written
In the case of word device memory, one word is expressed in 4-bit units in turn from the most significant bit in hexadecimal.
Ex.
When indicating the contents stored in the data registers D350 and D351
Device
Head device No.
code
D
*
0
0
44H
2AH
30H
30H 30H 33H 35H 30H 30H 30H 30H
5
6
A
b15
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 1 0 1 0 1 1 0 1 0 1 0 1 0 1 1 0 0 0 1
Indicates that D350 stores
"56ABH ("22187" in decimal)".
Use capitalized code for alphabetical letter.
When data other than integer value (real number, character string), is stored in the word device memory for
reading data, the stored value are read as integer value.
(Example 1) When a real number (0.75) is stored in D0 to D1, the value is read as the following integer value.
• D0 = 0000H, D1 = 3F40H
(Example 2) When a character string (12AB) is stored in D2 to D3, the character string is read as the following
integer value.
• D2 = 3231H, D3 = 4241H
Data in word units handled when reading and writing buffer memory areas is expressed in the same way as
the word device memory.
Number of
devices
0
3
5
0
0
0
0
2
32H
B
1
7
b15b14b13b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 1 1 1 0 0 0 0 1 1 1 1
Indicates that D351 stores
"170FH ("5903" in decimal)".
Data
Data
5
6
A
B
1
7
0
F
35H
36H
41H
42H
31H
37H
30H
46H
0
F
1: Indicates ON.
0: Indicates OFF.
3 MESSAGE FORMAT