hager tebis TX100 Operating Manual

hager tebis TX100 Operating Manual

Configurator
Hide thumbs Also See for tebis TX100:
Table of Contents

Advertisement

l
tebis Configurator
TX100
Operating manual
6T7639a

Advertisement

Table of Contents
loading

Summary of Contents for hager tebis TX100

  • Page 1 tebis Configurator TX100 Operating manual 6T7639a...
  • Page 2: Table Of Contents

    Summary 1. General information about the Tebis installations and their configuration ................ 3 1.1 The various product types ............................3 1.2 The different installation types............................. 3 1.3 General information about the configuration and the management of the Tebis installations........4 1.4 Presentation of the configuration tool TX100 ......................
  • Page 3: General Information About The Tebis Installations And Their Configuration

    1. General information about the Tebis installations and their configuration A Tebis installation is an electrical installation in which the products communicate with each other by means of a wired bus or by radio to send or receive commands. 1.1 The various product types A Tebis installation includes different product types, which can be classified: - According to their link to the KNX bus: •...
  • Page 4: General Information About The Configuration And The Management Of The Tebis Installations

    • Totally wired: all products of the installation communicate through the KNX cable • Mixed: the installation includes both RF and TP products: It is indispensable to install a media coupler in a mixed installation. This media coupler allows TP products and RF products to communicate with each other.
  • Page 5: Presentation Of The Configuration Tool Tx100

    - The Expert mode, it grants access to the objects and group addresses and it allows extending the installation with advan- ced Hager applications (visualisation, Internet gateway, weather station, etc.), creating complex logical functions or integra- ting the installation in systems configured with the ETS software.
  • Page 6: Continuing Or Modifying The Configuration Of A Saved Project

    If the charger is connected to the device when it is operating on dry-cell batteries and the selection switch is still in the rechargeable battery position, there is a risk of destroying the Tebis TX100 configurator. Charge the battery completely before the first use (3 h 30 min approximately).
  • Page 7: Usb Connector (Only On Tx100 Usb)

    2.1.3 USB connector (only on TX100 USB) Observe the direction of insertion of the USB connector: the USB symbol must always be directed upwards • Open flap A. • A USB connector allows connecting the TX100 with: - A USB stick (a stick is supplied with the TX100) using the 15 cm long cord supplied.
  • Page 8: Starting Up The Tx100

    2.2 Starting up the TX100 • Press the A button until the sound signal is activated in order to start or stop the configurator. • The TX100 displays temporarily a screen showing the software version. • The Project selection screen is displayed. First start-up: At the first start-up, the TX100 asks for the selection of the working language: •...
  • Page 9: Time And Day Setting

    Screen / Menu / Settings This screen allows selecting a specific setting. • Press the key to select the setting to be carried out. • Press the key to confirm your selection. key allows you to return to the previous screen. 2.3.2 Time and day setting Screen / Menu / Date and Time...
  • Page 10: Format Of The Ets Group Addresses

    2.3.5 Format of the ETS group addresses Screen / Menu / Settings / Address format: This function allows selecting the display or input format of the group addresses (on 2 or 3 levels). • Press the screen key corresponding to the desired format. screen key allows you to return to the previous screen.
  • Page 11: Coupler Selection

    2.3.8 Coupler selection Screen / Menu / Settings / Coupler selection This function allows associating a media coupler tool to the TX100. The coupler will be recognised automatically, avoiding the selection procedure. • Select the media coupler to be used by pressing its button until the red indicator turns on (4 s).
  • Page 12: Projects Management

    3. Projects management 3.1 Loading or creating a project when starting up the TX100 When starting up the TX100, a Project selection screen is displayed: it allows creating a new project or selecting an existing project. The content of the Project selection screen depends on whether an external memory is connected or not: Project selection screen when no external memory is connected: •...
  • Page 13: Old Format Project

    3.1.4 Old format project this project name corresponds to an old project format. The stored configuration was created with a TX100 with a version lower than V2.0. • Select Old format. • Press the key to confirm your selection. The "Warning" screen is displayed. •...
  • Page 14: Projects Management

    3.2 Projects management 3.2.1 Access to the projects management The TX100 is a tool that allows configuring and managing products: - Creation of new projects. - Storage of the current project in an external memory. - Loading of a project in the TX100 from an external memory. - Visualisation of a project.
  • Page 15 Menu selection / Project management / Save / Save as: This screen allows creating a new project file. A Project saving confirmation screen is displayed and a new project file is created under a name assigned automatically (here: Installation 001). •...
  • Page 16: Creation Of An Installation

    3.2.3 Creation of an installation Screen Menu/ Project management / Create: This screen allows creating a new project. A New project screen is displayed and a name is assigned automatically to the new project: here: Installation 001. The name of the project file can be modified from a PC. •...
  • Page 17 "Project name" selection A screen showing the project type (Installation or Learning) and its features is displayed. • Press the screen key to confirm. screen key allows you to return to the previous screen. If the installation was configured with another TX100, a Warning screen asks for confirmation before continuing: •...
  • Page 18: Deletion Of A Project

    The TX100 creates a new project in its internal memory. The current project possibly present in the internal memory will be deleted. A Warning screen allows authorising or not the deletion of the current project: • Press the NO screen key to retain the current project and return to the previous screen.
  • Page 19: Display Of The Basic Data Of A Project File

    3.2.6 Display of the basic data of a project file Screen Menu / Project management / Visualisation: This function allows displaying the data of the project files present in the external memory.This visualisation has no effect on the file of the current project, which is present in the internal memory of the TX100.
  • Page 20: Choice Of The On-Line Or Off-Line Configuration Mode

    4. Choice of the On-line or Off-line configuration mode After learning the installation and numbering the inputs and the outputs, the following operations are required: • Assign functions to the inputs. • Create links between the inputs and the outputs. These two operations can be performed both in On-line and Off-line mode: - In On-line mode, the configuration is downloaded as the functions are assigned to the inputs and the links are created: the installation may be tested at each step of the configuration in Auto mode.
  • Page 21: On-Line Configuration In Easy Mode Of A New Installation

    5. On-line configuration in Easy mode of a new installation 5.1 The various steps of the configuration To start a configuration, the TX100 configurator must first be able to communicate with the installation: this is the Installation coupling and assignation step. The configurator must then know the products present in the installation: this is the Product learning step.
  • Page 22: Coupling And Assigning The Tx100 To The Installation

    5.2.4 Checking the operating mode and the configuration status of the products • Make sure that all modular products equipped with Manu / Auto selection switches are in Auto mode. • Make sure that all products are in the Factory Reset status: •...
  • Page 23 After some seconds, the Installation type screen is displayed: • Press the YES screen key if the installation is a TP or mixed one. • Press the NO screen key if the installation is entirely a RF one. In this case, the Auto screen is displayed and switching to the Auto mode allows starting the configuration of the RF products.
  • Page 24: Learning Of The Installation And Numbering Of The Inputs And Outputs

    5.3.2 Creation of a coupler tool for the configuration of entirely TP installations When an installation only includes TP products, the media coupler may be removed after the configuration and it may be used to configure other TP installations. In this case, the media coupler is only used as a configuration tool associated with the TX100. This coupler is called "Coupler tool".
  • Page 25 At the end of the device-learning phase, the screen displays the characteristics of the first output as well as the number of outputs detected: A indicates that output 1 ( ) belongs to a TP product (symbol ) and that it has a lighting ON / OFF function (symbol B indicates that 95 outputs were detected in the installation.
  • Page 26 A Indicates that input 17 ( ) is a RF input (symbol ) and that no function was assigned yet (symbol B Indicates the number of numbered inputs. 5.4.3 Numbering of the inputs of the unidirectional RF products Follow the procedure below to number unidirectional RF input products: •...
  • Page 27 5.4.4 Learning of the installation with manual numbering of the outputs and inputs • Proceed according to the beginning of the above described procedure Learning with automatic numbering of the outputs. • When the Output numbering screen is displayed, press the YES screen key to start the learning procedure with manual numbering of the outputs.
  • Page 28 There are2 methods to number an output: - Method 1: • Press the pushbutton of the output to be numbered. A temporary screen indicates that the output has been detected and shows the number it will be given. If the output has no pushbutton, use method 2. - Method 2: Press the right keys to select the output.
  • Page 29: Assigning A Function To An Input

    At any time, the automatic numbering mode can be selected in order to finalize the numbering of the outputs. Go to the screen Menu / Advanced functions / Output numbering • Select Output numbering. • Press the key to confirm your selection. •...
  • Page 30 5.5.1 Assigning a function to a TP or bidirectional RF input As soon as an input is numbered, a function can be assigned: • Select the Prog mode (or the Num. mode). • Press the left keys to select the input. To select an input, it is also possible to activate the input directly on the product: its number is then displayed on the screen.
  • Page 31: Creation Of Links And Input Of Additional Parameters

    Example: A pushbutton ON function was assigned to the unidirectional RF input number 8. 5.6 Creation of links and input of additional parameters After the Product learning, Inputs/outputs numbering and Inputs function assignment phases, the Input/output links creation phase can begin. The TX100 offers several possibilities to create links: ➜...
  • Page 32 After having selected an input and an output. To create a simple link between this input and this output (for example between input 17 - pushbutton function and output 25 - lighting ON/OFF function). • Press briefly key The symbol appears to indicate that a link is to be created.
  • Page 33 Example: Preparation of 5 links. The last output selected is number 25. When all links have been prepared, press the key for a long time to confirm. At the end of the download, the symbol is changed in : the figures indicate that a link was created between 1 input and 5 output 5.6.3 Creating links by means of Copy/Paste of an input The Copy/Paste function allows copying all links of an input into another input.
  • Page 34: Creation Of Links And Input Of Additional Parameters

    • Press the left keys to select input 44. • Press the Paste screen key. screen key allows you to return to the previous screen Copy After an update time delay, the following screen is displayed. Input 44 is now linked to 16 outputs. Copying is finished.
  • Page 35 5.7.1 Setting the parameters which appear when creating a link. For some functions, a parameterizing screen is displayed when the link is confirmed. For example, for a link with a timer function, the following screen is displayed. This screen asks to set the duration of the timer. •...
  • Page 36: Vizualizing The Links

    • 5.8 Vizualizing the links This mode allows seeing all links of an installation. To have access to the visualisation mode from the Prog mode: • Press the Auto screen key to go to the Auto mode. • In Auto mode, press the central screen key Visu. The links can be visualized: - via the inputs: by selecting the no.
  • Page 37: Modifying The Configuration Of An Installation

    7. Modifying the configuration of an installation 7.1 General indications about the modifications of a KNX installation A KNX installation is made up of 3 elements. - A physical installation: pushbuttons, output modules, wires, ... - A configuration, which is memorised in the products of the installation. - A project file.
  • Page 38 7.2.2 Removing all links of an installation This function removes all programmed links. Go to the screen Menu / Instal. Management / Delete links: • Press the YES key screen to remove all links. A sound signal indicates that all links have been removed. A double sound signal indicates an error.
  • Page 39: On-Line Configuration Of A New Installation In Expert Mode

    Grants access to the group address given during programming in Standard mode in order to set up links between a Tebis TX installation (TP, radio KNX) and Hager devices such as technical alarms, displays, Internet gateways. - Programming of mixed installations (KNX and Tebis).
  • Page 40: Description Of The Expert Mode

    8.2 Description of the Expert mode 8.2.1 Activation and access to the Expert mode Press the menu key of the keypad or the "menu access" key located on the right side of the TX100. • Select Expert / Standard to activate the Expert mode. •...
  • Page 41 8.2.2 Inputs, outputs and object selection • Inputs and outputs selection This selection may be done either in Prog Expert or in Prog Easy. • Press the left keys to select an input. • Press the right keys to select an output. The list on the input side is of the +Info type: it displays both the inputs and the status indications of the outputs (the outputs are marked with the symbol following the...
  • Page 42 In this case, the Group address screen is displayed (the exact display of the address depends on the format). The group addresses can be set using the keys or with the numerical keypad of the TX100. • Press the left keys to select a field of the address.
  • Page 43: Configuring In Expert Mode

    8.3 Configuring in Expert mode The Expert mode allows 2 types of extended configurations. - Use an object configured with the TX100 in another application: Visualisation, etc. - Configure special links with the TX100. 8.3.1 Using a RF product object in another application •...
  • Page 44 • Press the key for a long time • An Update screen is displayed. • A sound signal confirms the addition of the group address. • Return to Auto mode. 8.3.2 Creating links in Expert mode To create a link in Expert mode, objects must be linked assigning them the same group address. •...
  • Page 45 • Select the object to be linked for the output. • Press briefly key • Press the Add screen key. • Add the same address 4/122. • Press the Confirm screen key to return to the Prog Expert screen. • Download the address with a long key press on •...
  • Page 46: Maintenance And Adjustment Help Tools

    9. Maintenance and adjustment help tools The TX100 has several installation maintenance and configuration help tools for: - The management of the products of an installation. - The management of the installations. - Carrying out measurements. - Making simulations. - Updating the software of the TX100. - Learning an installation.
  • Page 47 To reset a product which does not belong to the installation: • Select Not install. with the key. • Press the key to confirm your selection. A Reset screen with the list of the product types is displayed: • Select the type of the product: RF or TP Depending on the product, a specific status must be activated (refer to the start-up manual of the products or to Annex 1): - TP device: press on the physical addressing button and confirm.
  • Page 48 9.1.3 Creation of a RF repeater This function allows activating or inhibiting the repeater function of a bidirectional RF product. Screen / Menu / Device management / Repeater The list of the bidirectional RF products of the installation is displayed. •...
  • Page 49: Installation Management

    9.2 Installation management Screen / Menu / Instal. Management: This screen gives acces to the following items: - Reset: allows resetting all products of the installation into their factory condition. - Coupler selection: allows assigning any coupler to the installation. - Installation update: allows deleting from the project files the products which are not used in the current installation.
  • Page 50 9.2.4 Information about the installation Screen / Menu / Instal. Management / Information. This function gives general information about the installation. 9.2.5 Downloading an installation Screen / Menu / Instal. Management / Download): This function allows starting or resuming a download for all products of the installation. •...
  • Page 51: Updating The Software Of The Tx100

    9.3 Updating the software of the TX100 The software of the TX100 can be updated from an update file stored on an external memory, USB, SM, or on a PC. Follow the steps below: • Switch the TX100 off if it is on by pressing the ON/OFF pushbutton for a long time. •...
  • Page 52 The update procedure is started when the YES screen key is pressed. A Warning screen informs that the current project stored in the TX100 will be deleted: Press the YES screen key to confirm. Press the NO screen key to cancel and to return to the previous screen. A wait screen is displayed until the end of the update: •...
  • Page 53 The following screen indicates that the link from the TX100 to the PC is being established. The following screen is displayed when the link is established: On the PC, paste the update file in directory TX100 HAGER. TX100 USB 6T7639a...
  • Page 54: Learning An Installation

    After the confirmation, a wait screen is displayed until the end of the update: When the update is completed, press the key to restart the TX100. If there is no update file in the TX100 HAGER directory, the following screen is displayed. 9.4 Learning an installation This function allows "re-learning"...
  • Page 55 To start learning an installation. Screen / Menu / Instal. Management • Select Learn installation with the key. • Press the key to confirm your selection. The Learn installation screen is displayed: 3 items are available: - Creation to create a project of the Learning type. - Resume to go on learning an already started project.
  • Page 56 The Learning project is now created. The Installation type screen is displayed: • Press the YES screen key if the installation is a TP or mixed one. • Press the NO screen key if the installation is entirely a RF one: See.
  • Page 57 The Auto screen is displayed at the end of the update: At this point, the installation has been completely learnt, but it is not validated yet. The Prog mode is not accessible. • Press the Visu screen key to display the inputs, the outputs, the functions and the links.
  • Page 58 The following screen is displayed: The Learn installation screen displays: • the total number of RF products found. • the total number of TP products found. • the Error lines indicate the number of products which are only partly learnt. •...
  • Page 59 The Learn installation screen is displayed: • Press the YES screen key if the installation only includes bidirectional RF products. • Press the NO screen key if the installation only includes TP and/or unidirectional RF products. 9.4.6 Validation Tha validation allows to finalise the learning and to turn the Learning-type installation into a normal installation. Go to Screen / Menu / Instal.
  • Page 60: Measuring Tools

    9.5 Measuring tools Various measurements can be performed in an installation to adjust or to optimise the installation: - Measurement of the RF noise. - Measurement of the Konnex traffic. - Measurement of the transmitting power of a RF emitter and of the reception sensitivity of a RF receiver. RF noise and Konnex traffic measurement is accessible via the Menu key.
  • Page 61 9.5.3 Measurement of the Konnex traffic Screen / Menu / RF tools / Konnex traffic This function allows you to measure the RF level emitted by any Konnex transmitter. A measuring cycle starts as soon as the function is selected. At every receipt of a telegram, the configurator displays: - the serial number of the emitting device.
  • Page 62: Simulation

    9.6 Simulation The Simulation function allows to: • Simulate a repeater: In this case, the TX100 behaves like a repeater. It is possible to determine the ideal location of a repeater product. • Simulate an input: In this case, the TX100 behaves like an input. It is possible to test the links set up with this input. There are 2 ways to start a simulation: •...

Table of Contents