3. How to install the indoor unit

3-1-3. Placing the Unit Inside the Ceiling

This unit is equipped with the drain pump. Check a tape measure or carpenter's level.
Before installing the ceiling panel, complete the work of drain pipe and refrigerant pipe installation.
(1)
When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the supplied full-scale
installation diagram. (Fig. 2-21)
Tubing and wiring must be laid inside the ceiling when
suspending the unit. If the ceiling is already constructed,
lay the tubing and wiring into position for connection to
the unit before placing the unit inside the ceiling.
(2)
The length of suspension bolts must be appropriate for a
distance between the bottom of the bolt and the bottom
of the unit of more than 18 mm as shown in Fig. 2-21.
1
(3)
Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown in
Fig. 2-22. Use 1 nut and 1 washer for the upper side, and
2 nuts and 1 washer for the lower side, so that the unit
will not fall off the suspension lugs.
2
(4)
Adjust so that the distance between the unit and the
ceiling bottom is 12 to 17 mm. Tighten the nuts on the
upper side and lower side of the suspension lug.
(5)
Remove the protective polyethylene used to protect the
fan parts during transport.
3
(6)
Check with a tape measure or carpenter's level.

3-1-4. How to Process Tubing

4
Refer to the TECHNICAL DATA "TD831159".
5
6
7
8
9
Screw for
attaching paper
(4 points)
Over 18 mm
Ceiling

Full-scale installation diagram

(printed on top of container box)
Nuts and washers
(use for upper and lower)
Double nut
2-16
Design of VRF SYSTEM
Ceiling
Air
conditioner
Paper model for
installation
Open the ceiling
as large as this
paper outline
Air
conditioner
Paper model
for installation
Fig. 2-21
Suspension bolt
Suspension lug
Notch
12 – 17 (mm)
Fig. 2-22