Efficiency - Siemens SITOP PSU100S Operating Instructions Manual

Table of Contents

Advertisement

When the output voltage falls below approx. 10 V, the 6EP1336-2BA10 device switches off,
and automatically restarts. This response is repeated as long as the overload condition is
present.
6.3

Efficiency

Efficiency at Ua rated, Ia rated
120 V / 230 V AC approx.
Power loss at Ua rated, Ia rated
120 V / 230 V AC approx.
Power loss when idling
120 V / 230 V AC approx.
Efficiency at Ua rated, Ia rated
120 V / 230 V AC approx.
Power loss at Ua rated, Ia rated
120 V / 230 V AC approx.
Power loss when idling
120 V / 230 V AC approx.
80
Figure 6-9
SITOP PSU100S
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1332-2BA20
83 % / 85 %
11 W / 10 W
1.7 W / 1.2 W
90
89
88
87
2,5 A
86
85
84
83
82
1,25 A
81
100
120
80
Efficiency 6EP1332-2BA20
6EP1333-2BA20
86 % / 87 %
18 W / 16 W
1.8 W / 1.3 W
6EP1322-2BA00
82 % / 83 %
16 W / 15 W
1.5 W / 1.0 W
1,25 A
1,875 A
140
160
180
200
Technical data
6EP1334-2BA20
6EP1336-2BA10
89 % / 90 %
89 % / 90 %
27 W / 25 W
59 W / 53 W
3.0 W / 2.4 W
4.1 W / 3.6 W
6EP1323-2BA00
86 % / 87 %
27 W / 15 W
2.8 W / 2.3 W
2,5 A
1,875 A
220
240
260
280
6.3 Efficiency