Technical data
6.2 Output
Duration of the overload
capability, overcurrent / for a
short circuit while powering up
Short-time overload current / for
a short circuit in operation /
typical
Duration of the overload
capability, overcurrent / for a
short circuit in operation
Can be connected in parallel to
increase the power rating
Number of devices that can be
connected in parallel to increase
the power rating, units
Output characteristic
Capacitive load, max.
Figure 6-2
44
Remark
Remark
Startup delay/voltage rise
6EP1322-2BA00
800 ms
once-only
26 A
800 ms
once-only
Yes
2
see diagram, output
characteristic for 6EP1322-
2BA20 (Page 46)
2 mF/A
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1323-2BA00
800 ms
once-only
48 A
800 ms
once-only
see diagram, output
characteristic for 6EP1323-
2BA20 (Page 46)
SITOP PSU100S