Technical data
6.2 Output
Response when
switching on/off
Starting delay, max.
Start delay, typ.
Voltage rise
120 V / 230 V AC max.
Voltage rise
120 V / 230 V AC typ.
Rated current Ia rated
Current range
Remark
Output active power /
typical
Overload capability
(Extra Power)
Short-time overload
current / for a short
circuit when powering
up / typical
Duration of the
overload capability,
overcurrent / for a
short circuit while
powering up
Remark
Short-time overload
current / for a short
circuit in operation /
typical
Duration of the
overload capability,
overcurrent / for a
short circuit in
operation
Remark
Can be connected in
parallel to increase the
power rating
Number of devices
that can be connected
in parallel to increase
the power rating, units
42
6EP1332-2BA20
Overshoot of Ua<720 mV
300 ms
200 ms
100 ms
15 ms
2.5 A
0...2.5 A
3 A to +45° C
+60 to +70 °C;
derating: 3 % Ia
rated/K
60 W
3.75 A for 5 s/min
9 A
800 ms
once-only
9 A
800 ms
once-only
Yes
2
6EP1333-2BA20
300 ms
160 ms
100 ms
15 ms
5 A
0...5 A
6 A to +45° C
+60 to +70 °C;
derating: 3 % Ia
rated/K
120 W
7.5 A for 5 s/min
18 A
800 ms
once-only
18 A
800 ms
once-only
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1334-2BA20
300 ms
150 ms
100 ms
20 ms
10 A
0...10 A
12 A to +45° C
+60 to +70 °C;
derating: 3 % Ia
rated/K
240 W
15 A for 5 s/min
33 A
800 ms
once-only
33 A
800 ms
once-only
6EP1336-2BA10
No overshoot of Ua
(soft start), with the
exception of a
capacitive load
1.5 s
500 ms
500 ms
50 ms
20 A
0...20 A
24 A to +45° C
+60 to +70 °C;
derating: 5 % Ia
rated/K
480 W
30 A for 5 s/min
35 A
100 ms
every 2.5 s
35 A
100 ms
every 2.5 s
SITOP PSU100S