Command Set

4.4 Analog I/O Module Command set

4.4.1
%AANNTTCCFF
Configuration
Name
Sets address, input range, baud rate, data format, checksum
Description
status, and/or integration time for an analog input module.
%AANNTTCCFF(cr)
Syntax
% is a delimiter character.
AA(range 00-FF) represents the 2-character hexadecimal
address of the analog input module you want to
configure.
NN represents the new hexadecimal address of the analog
input module. Range is from 00h to FFh.
TT represents 00.
CC represents the baud rate code.
FF is a hexadecimal number that equals the 8-bit parameter
representing the data format, checksum status and
integration time.
The layout of the 8-bit parameter is shown in figure
4-1. Bits 2 through 5 are not used and are set to 0. (cr)
is the terminating character, carriage return (0Dh)
Figure 4-1 Data format for 8-bit parameter