Chapter 6
Certification
Test
IEC 61000-4-29
IEC 61000-4-11
IEC 60255-5
a
Siemens specified severity level.
IEEE 1613 EMC Immunity Type Tests
NOTE
The RUGGEDCOM RMC20 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
ESD
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Dielectric Strength
26
Description
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
DC Power Ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
AC Power Ports
30% for 1 period, 60% for 50 periods
100% for 5 periods,
100% for 50 periods
Signal Ports
2 kV  (Fail-Safe Relay output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV  (Fail-Safe Relay Output)
DC Power Ports
AC Power Ports
2.5 kV common, 1 kV differential mode @ 1MHz
2.5 kV common, 1 kV differential mode @ 1MHz
Installation Guide
Test Levels
1000 A/m for 1 s
1.5 kV
2 kV
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV common mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV
1.5 kV
2 kV
EMC and Environmental Type Tests
RUGGEDCOM RMC20
Severity Levels
5

Hide quick links:

Advertisement

Table of Contents
loading