Compressor Electrical Data 30Hxc + Option 150/150A - Carrier 30HXC Installation, Operation And Maintenance Instructions

Screw compressor water-cooled liquid chillers
Table of Contents

Advertisement

The 30HXC 080-375 units for high condensing temperatures are
directly derived from the standard models. Their application
range is the same as that of the standard units, but permits
operation at condenser leaving water temperatures up to 63°C.
The PRO-DIALOG control offers all the advantages of the
standard units, plus control of the condenser leaving water
temperature.
The main modifications are:
Use of high lift compressors (example: 06NA2300S5N
instead of 06NW 2300S5N).
Modification of electrical components to operate with
compressors for high condensing temperatures.
Modification of heat exchangers to meet pressure code
requirements (if necessary).
Option 150
These units are designed for traditional applications for water-
cooled units, but for higher condender leaving water temperatures
than 50°C.
Like the standard units they are equipped with condenser entering
and leaving water sensors.
It is possible to control the machine at the condenser water outlet,
requiring a factory configuration change and the use of a heating/
cooling inlet reversing device.
Option 150A
These units are designed for water-to-water heat pumps.
They are factory configured as heat pumps (heating/cooling control
as a function of the remote reversing device). The condenser
incorporates thermal insulation that is identical to that of the
evaporator.

4.5 - Compressor electrical data 30HXC + option 150/150A

Reference
Size
06NA2146S7N
39
06NA2174S7N
46
06NA2209S7N
56
06NA2250S7N
66
06NA2300S5N
80
06NA2300S5E
80+
Legend
06NA
- Compressor for air-cooled units
N
- Non-economized compressor
E
- Economized compressor
I nom.
- Average current draw of the compressor at Eurovent conditions (A)
MHA
- Must hold amperes (maximum operating current) at 360 V (A)
LRA
- Locked rotor current with across-the-line start (A)
LRA (Y)
- Locked rotor current at reduced current (star/delta start-up mode) (A)
LRA (S) 1 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit
16
I nom.
MHA
72
99
87
124
103
148
124
177
149
207
174
258
Technical information
All information is identical to that of the standard 30HXC units,
except for the following paragraphs.
Selection
There are no nominal conditions for this unit type. The selection
is made using the current electronic catalogue.
Dimensions
These are identical to those of the standard 30HXC units. The
only difference is in the diameter of the incoming field wiring
connection, described in the chapter "Recommended selection".
Refer to the dimensional drawings for these units, before
proceeding with the wiring.
Compressor
See table in chapter 4.5.
Options and accessories
All options available for the standard 30HXC units are compatible,
except low-temperature option 5 for the evaporator available in
the special unit.
ATTENTION: If units have two different operating modes - one
with high condensing temperature and the other with low
condensing temperature - and the transition is made with the
unit in operation, the temperature must not vary by more than
3K per minute. In cases where this is not possible, it is
recommended to go through a unit start/stop switch (remote
start/stop available for standard units).
LRA
LRA (Y)
605
191
715
226
856
270
960
303
1226
387
1265
400
LRA (S) 1 cp.
LRA (S) 2 cp.
NA
NA
NA
NA
330
480
435
575
490
610
510
660

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents