CONTROLLER MOUNTING BRACKET

18mm
Installed controller height 18mm
above top of mounting bracket.

ELECTRIC WIRING WORK

PRECAUTIONS
Precaution for wiring on site
Do not clamp remote controller cords together with wires connecting the units together. Doing so may cause malfunction.
Remote controller cords and wires connecting the units should be located at least 50 mm from other electric
wires. Failure to follow this guideline may result in malfunction due to electrical noise. Read the notes mentioned
below when wiring to the power supply terminal block. Precautions to be taken for power supply wiring. (Use a
round crimp-style terminal for connection to the power supply terminal block. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instructions.)
Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may
cause overheating.)
When connecting wires of the same gauge, connect them according to the figure.
Make certain that prescribed wires are used, carry out complete connections, and secure the wires so that
outside forces are not applied to the terminals.
Round crimp-style
terminal
CAUTION
After connecting the wires, be sure that no pressure is applied to the wire connections by using cable ties (field
supplied) and securing them to the anchor points. Also, when wiring, make sure the cover of the terminal box fits
snugly by arranging the wires neatly and attaching the terminal box cover firmly. When attaching the terminal box
cover, make sure no wires get caught under the edges.
Make sure the remote control cord, the wiring between the electrical boxes, and other electrical wiring do not pass
through the same locations outside the unit, separating them by at least 50 mm, otherwise electrical noise
(external static) could cause interference to the control system.
All field supplied parts and materials and electric works must conform to local codes. (ie. AS / NZS 3000)
Use copper wire only.
For electric wiring work, refer also to the "WIRING DIAGRAM" label attached to the electrical box cover.
For remote controller wiring details, refer to this installation manual.
All wiring must be performed by an authorised electrician in accordance with local codes. (ie. AS / NZS 3000)
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Ensure that the air conditioner and zone controller box are effectively earthed.
14
Hole ush
with
HOLE
top of
IN
bracket
WALL
Do not cut hole above height of
bracket.
Connect wires of
the same gauge to
both sides
Electric wire
CORRECT
Earth shield spade receptacle is
used only when extension cable
(BRCW902A15) is installed. When
BRCW902A15 is not used tuck
insulated spade receptacle in wall
cavity
Do not connect
Do not connect
wires of the same
wires of different
gauge to one side
gauges
WRONG