No Heat.
PROBLEM
Table
12 - Heating
Service
Analysis
CAUSE
Power failure.
Fuse blown or circuit breaker tripped.
CB1, CB2, CB3.
Thermostat
not calling for heating.
No 24 vac at primary contactor.
No power (high voltage) to L2 of
primary contactor.
Bad electrical elements.
REMEDY
Call power company.
Replace fuse or reset circuit breaker.
Check thermostat.
Check transformer and circuit breaker.
Check safety switches, one shot backup,
and auto limit.
With power off, remove high voltage wires and
check resistance of heater. Replace if open.
EconoMi$er
IV Troubleshooting
EconoMi$er
IV Preparation
This
procedure
is used
to
prepare
the
EconoMi$er
IV
for
troubleshooting.
No
troubleshooting
or
testing
is
done
by
performing
the following
procedure.
NOTE:
This
procedure
requires
a 9-v
battery,
1.2 kilo-ohm
resistor,
and a 5.6 kilo-ohm
resistor
which
are not supplied
with
the EconoMi$er
IV.
IMPORTANT:
Be
sure
to
record
the
positions
of
all
potentiometers
before
starting troubleshooting.
1. Disconnect
power
at TR and TRI.
All LEDs should
be off.
Exhaust
fan contacts
should be open.
2. Disconnect
device
at P and PI.
3. Jumper
P to PI.
4. Disconnect
wires at T and T1. Place
5.6 kilo-ohm
resistor
across T and T1.
5. Jumper
TR to 1.
6. Jumper
TR to N.
7. If connected,
remove
sensor
from
terminals
So
and
+.
Connect
1.2 kilo-ohm
4074EJM
checkout
resistor
across
terminals
So and +.
8. Put 620-ohm
resistor
across terminals
SR and +.
9. Set
minimum
position,
DCV
set
point,
and
exhaust
potentiometers
fully CCW (counterclockwise).
10. Set
DCV
maximum
position
potentiometer
fully
CW
(clockwise).
11. Set enthalpy
potentiometer
to D.
12. Apply
power
(24 vac) to terminals
TR and TRI.
Differential
Enthalpy
To check differential
enthalpy:
1. Make sure EconoMi$er
IV preparation
procedure
has been
performed.
2. Place 620-ohm
resistor
across
So and +.
3. Place 1.2 kilo-ohm
resistor
across SR and +. The Free Cool
LED should be lit.
4. Remove
620-ohm
resistor
across So and +. The Free Cool
5.
and
wiring
to
normal
LED should turn off.
Return
EconoMi$er
IV
settings
after completing
troubleshooting.
Single
Enthalpy
To check single enthalpy:
1. Make sure EconoMi$er
IV preparation
procedure
has been
performed.
2. Set the enthalpy
potentiometer
to A (fully
CCW).
The Free
Cool LED should be lit.
3. Set the enthalpy
potentiometer
to D (fully
CW). The Free
Cool LED should turn off.
4. Return
EconoMi$er
IV
settings
and
wiring
to
normal
after completing
troubleshooting.
DCV
(Demand Controlled
Ventilation)
and
Power
Exhaust
To check DCV and power
exhaust:
1. Make sure EconoMi$er
IV preparation
procedure
has been
performed.
2. Ensure
terminals
AQ and AQI
are open.
The LED for both
DCV
and Exhaust
should
be off. The actuator
should
be
fully closed.
3. Connect
a 9-v
battery
to AQ
(positive
node)
and AQ1
(negative
node).
The
LED
for both
DCV
and
Exhaust
should
turn on. The actuator
should
drive
to between
90
and 95% open.
4. Turn the Exhaust
potentiometer
CW until the Exhaust
LED
turns
off.
The
LED
should
turn
off
when
the
potentiometer
is approximately
90%.
The actuator
should
remain
in position.
5. Turn the DCV
set point potentiometer
CW until the DCV
LED
turns
off. The DCV
LED
should
turn off when
the
potentiometer
is approximately
9 v. The
actuator
should
drive fully closed.
6. Turn the DCV and Exhaust
potentiometers
CCW
until the
Exhaust
LED turns on. The exhaust
contacts
will close 30
to 120 seconds
after the Exhaust
LED turns on.
7. Return
EconoMi$er
IV
settings
and
wiring
to
normal
after completing
troubleshooting.
DCV
Minimum
and Maximum
Position
To check the DCV minimum
and maximum
position:
1. Make sure EconoMi$er
IV preparation
procedure
has been
performed.
2. Connect
a 9-v
battery
to AQ
(positive
node)
and AQ1
(negative
node).
The
DCV
LED
should
turn
on.
The
actuator
should
drive to between
90 and 95% open.
3. Turn
the
DCV
Maximum
Position
potentiometer
to
midpoint.
The actuator
should drive to between
20 and 80%
open.
4. Turn
the DCV
Maximum
Position
potentiometer
to fully
CCW. The actuator
should drive fully closed.
5. Turn the Minimum
Position
potentiometer
to midpoint.
The
actuator
should
drive to between
20 and 80% open.
6. Turn
the Minimum
Position
Potentiometer
fully
CW. The
actuator
should
drive fully open.
7. Remove
the jumper
from
TR and N. The actuator
should
drive fully closed.
8. Return
EconoMi$er
IV
settings
and
wiring
to
normal
after completing
troubleshooting.
Mixed
Air
Input
To check mixed
air input:
1. Make sure EconoMi$er
IV preparation
procedure
has been
performed.
2. Set the Enthalpy
potentiometer
to A. The Free
Cool LED
turns on. The actuator
should drive to between
20 and 80%
open.
45