Mitsubishi PEFY-P06NMAU-E2 Operation Manual page 10

City multi
Table of Contents

Advertisement

Available languages

Available languages

Item
Power source
Cooling capacity*
1
/ Heating capacity*
Height
Dimension
Width
Depth
Net weight
Airfl ow rate(Low-Mid-High)
Fan
External staticpressure*
Sound level(Low-Mid-High)*
2
*
3
Filter
Notes: *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 80 °F (26.7 °C) D.B./67 °F (19.4 °C) W.B.
Heating: Indoor: 70 °F (21.1 °C) D.B.
Pipe length: 7.5 m (24-9/16 ft)
*2 The external static pressure is set to 0.20 in. WG (50 Pa) at factory shipment.
*3 The operating noise is the data that was obtained in an anechoic room.
10
Model
P36NMAU-E2
Btu/h
36,000/40,000
1
kW
10.6/11.7
mm[in]
mm[in]
1,400[55-1/8]
mm[in]
kg[lb]
39[86]
CFM
812-989-1,165
in.WG
2
[Pa]
dB(A)
32-37-41
Outdoor: 95 °F (35 °C) D.B.
Outdoor: 47 °F (8.3 °C) D.B./43 °F (6.1 °C) W.B.
Height difference: 0 m (0 ft)
P48NMAU-E2
P54NMAU-E2
208, 230V 60Hz
48,000/54,000
54,000/60,000
14.1/15.8
15.8/17.6
250[9-13/16]
1,600[63]
732[28-7/8]
42[93]
989-1,201-1,412
1,042-1,254-1,483
0.14-0.20-0.28-0.40-0.60
[35/50/70/100/150]
35-40-44
36-41-45
Standard fi lter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents