Pentair FLECK NXT TIMER Service Manual page 9

2 line/ 16 character full text lcd backlit display
Table of Contents

Advertisement

VALVE ADDRESS:
#2
MASTER PROGRAMMING MODE FLOW
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
CHART continued
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
REGEN TYPE:
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
VALVE TYPE:
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
REGENERANT FLOW:
DOWNFLOW
Options: Downflow (Default)
Up Flow
UF Fill First
REMOTE SIGNAL
START: 00:06:00
Options: Off (Default)
00:00:00 (Hours:Minutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
DISPLAY FORMAT:
US-GALLONS
Options: U.S. - Gallons (Default)
Eu Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
UNIT CAPACITY:
00000000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1 to 198,000 grams CaCO3 Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
CAPACITY SAFETY
FACTOR:
00%
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Range: 1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
Examples: Default will need to be changed before next step
Brings 2nd valve In Service after 125 gpm
Brings 2nd valve In Service after 400 lpm
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
TRIP DELAY 1:
30 SECONDS
Example:
Valve Address #2 (Second Control Valve) (Default)
Example:
2 Valves in the System (Default)
Example:
Time Clock Delayed (Default)
Example:
2750 (Default)
Example:
Downflow (Default)
Example:
00:06:00
(Hours:Minutes:Seconds)
Example:
U.S. Gallons (Default)
Example:
Grains (Default)
Example:
00% (Default)
Example:
15 GPG (U.S. Format) (Default)
[000] = (Default)
[125]
[400]
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
Trip Points 1, 2, and 3 (System 14 only)
REGENERANT FLOW:
This program step selects up to three Trip Points programmed
DOWNFLOW
on the master timer only (Valve Address #1).
Options: Downflow (Default)
Up Flow
The actual required number of Trip Points in a system is one
UF Fill First
less than the number of valves in the system.
Trip Point 1 represents the system flow rate at which a second
REMOTE SIGNAL
valve will be brought In Service or Standby.
START: 00:06:00
Options: Off (Default)
Trip Point 2 represents the system flow rate at which a third
00:00:00 (Hours:Minutes:Seconds)
valve will be brought In Service or Standby.
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
Trip Point 3 represents the system flow rate at which a fourth
valve will be brought In Service or Standby.
DISPLAY FORMAT:
US-GALLONS
Trip Point 1
Trip Point 2
Options: U.S. - Gallons (Default)
Eu Metric - Liters (Metric)
Range:
U.S.: Value of Trip Point
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
1 – 997 GPM
1 plus 1 to 998
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
Range:
Metric: Value of Trip
0001 – 3997 Lpm
Point 1 plus 1 - 3998
UNIT CAPACITY:
00000000 GRAINS
Trip Delays 1, 2, and 3 (System 14 only)
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
This program step selects each Trip Delay time that is
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
addressed with each Trip Point and will be programmed on
1 to 198,000 grams CaCO3 Capacity in Metric Format
the Master timer only (Valve Address #1). The Trip Delay time
NOTE: Use the Shift button to move to the left.
represents a minimum amount of time the system flow rate
is required to be equal or greater than the Trip Points to bring
CAPACITY SAFETY
a unit In Service. It also is the minimum amount of time the
FACTOR:
00%
system flow rate is required to be less than the Trip Points to
Range: 0 to 50%
remove a unit from In Service to Standby.
NOTE: Use the Shift button to move to the left.
Trip Delay 1
Trip Delay 2
FEED WATER
HARDNESS: 15 GPG
Default: 30 Seconds
Range: 1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
Range:
NOTE: Use the Shift button to move to the left.
30 - 99 Seconds
30 - 99 Seconds
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
Examples: Default will need to be changed before next step
Brings 2nd valve In Service after 125 gpm
Brings 2nd valve In Service after 400 lpm
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to move one space to the left.
TRIP POINT 2:
gpm
Examples: Brings 3rd valve In Service after 250 gpm
Brings 3rd valve In Service after 900 lpm
Range:
Trip Point 1 + 1 to 998 gpm (U.S. Format)
Trip Point 1 + 1 to 3998 lpm (Metric Format)
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 3:
gpm
2750 (Default)
Example:
Downflow (Default)
Example:
00:06:00
(Hours:Minutes:Seconds)
Example:
U.S. Gallons (Default)
Trip Point 3
U.S.: Trip Point 2 plus
1 to 999
Metric: Trip Point 2
plus 1 - 3999
Example:
Grains (Default)
Example:
00% (Default)
Trip Delay 3
Example:
15 GPG (U.S. Format) (Default)
Range:
Range:
30 - 99 Seconds
[000] = (Default)
[125]
[400]
[250]
[900]
Fleck 3200 NXT • 9