User Programming Mode Flow Chart; Diagnostic Programming Mode Flow Chart - Pentair FLECK NXT TIMER Service Manual

2 line/ 16 character full text lcd backlit display
Table of Contents

Advertisement

MAXIMUM FLOW
MASTER PROGRAMMING MODE FLOW
RATE: 0000 gpm
CHART continued
Range:
20 - 2000 gpm (U.S. Format)
20 - 2000 L (Metric Format)
NOTE: Only displayed if "Generic" is chosen for the flow meter.
ADD 01 GALLONS
EVERY 001 PULSES
Options: Gallons (U.S. Format)
Liters (Metric Format)
Range:
1 - 255 Gallons (U.S. Format)
1 - 255L (Metric Format)
Pulses: 1 - 255
NOTE: Only displayed if "Generic" is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...

USER PROGRAMMING MODE FLOW CHART

Entering User Programming Mode
Hold the Set Up and Set Down buttons for 5 seconds.
NOTE: User Mode is only displayed when a metered option
is chosen under System Type. Depending on current
option settings, some displays cannot be viewed or
set.
NOTE: User Mode cannot be entered on the Lag unit for
System 6.
FEED WATER
HARDNESS: gpg
REGENERATION DAY
OVERRIDE: OFF
REGENERATION DAY
OVERRIDE:99 DAYS
REGENERATION
TIME: 02:00AM
Example:
Maximum Flow Rate of 0 gpm
Example:
Add 1 Gallon for Each Pulse in U.S. Format
Example:
Master Programming Mode is Exiting
mg/l
DIAGNOSTIC PROGRAMMING MODE
FLOW CHART
Entering Diagnostic Programming Mode
1. Push and release the "D" button.
2. Press the Extra Cycle button once per display until all
displays are viewed and Normal Display is resumed.
3. Push and release the"D" button at anytime during
diagnostic mode and the timer will exit the mode.
4. Depending on the current controller programming, certain
displays may not be able to be viewed or set.
Overview Diagnostic Mode
The current diagnostic will be displayed until Extra Cycle key is
pressed. There is no time limit on each display. The timer will
display local information, not system information. In the event
of a regeneration occurring while displaying diagnostics, the
regeneration step and time remaining will be displayed. When
regeneration has been completed, the display will return to the
main screen.
CURRENT FLOW
RATE:
0 gpm
PEAK FLOW RATE:
0 gpm
TOTALIZER:
130 g
LAST TWO REGENS:
0 HOURS
LAST REGEN
0 HOURS
VOLUME REMAIN:
1000 g
NOTE: If a System 6, Unit #1 of "Tank Remaining" will display "System
Remaining".
VALVE ADDRESS
#2
VERSION:
X.XX
Example:
Flow rate at this time.
Example:
Peak flow since last regeneration.
Example:
Gallons at the outlet since installation.
Example:
Hours between the last regeneration and the
one before it.
Example:
Hours since last regeneration.
Example:
Volume remaining (can be adjusted).
Example:
Controller unit number.
Example:
Installed software level of the controller in use.
Fleck 3200 NXT • 11