System Definitions - Pentair FLECK NXT TIMER Service Manual

2 line/ 16 character full text lcd backlit display
Table of Contents

Advertisement

SYSTEM DEFINITIONS

System
System
Number
Description
Controls
4
Single Unit
5
Interlocked
2, 3, or 4
6
Series
2, 3, or 4
Regeneration
7
Twin
Alternating
9
Multiple Tank
2, 3, or 4
Alternating
14
Demand
2, 3, or 4
Recall
4 • Fleck 3200 NXT
# of
Type
Tanks/
1
Time Clock: No Meter
Immediate: One Meter
Delayed: One Meter
Remote Signal Start: No Meter
Immediate: All Meters
Remote Signal Start: No Meter
Immediate: One Meter
Delayed: One Meter
Remote Signal Start: No Meter
2
Immediate: One Meter
Remote Signal Start: No Meter
Immediate: All Meters
Remote Signal Start: No Meter
Immediate: All Meters
Operation Discussion
Single tank configuration.
All tanks in parallel supplying treated water. Each unit in the system
will have its own flow meter/sensor input. The control will delay the
start of Regeneration if another unit is already in Regeneration. Once
that unit has completed a Regeneration cycle, and has returned to
Service,the unit with longest regeneration queue time will begin
Regeneration. No more than one unit will be in Regeneration at a time.
All tanks in parallel supplying treated water. Only #1 control will
monitor flow meter/sensor input. When a regeneration is required
for the system, it will regenerate valve address #1 first, immediately
followed by #2, then #3, then #4 if installed. No more than one unit
will be in Regeneration at a time.
One tank online supplying treated water, one tank in Standby. Only
#1 control will monitor its flow meter/sensor input. Regeneration of
a unit will begin after the other control has left Standby and returned
to Service. When the Regeneration cycle is complete, the regenerated
unit will enter Standby. Standby on each tank is controlled by the lower
drive output terminals on the NXT circuit board.
One, two, or three tanks online supplying treated water, one tank in
Standby. Meter/sensor input is required on each tank. Regeneration of
a unit will begin after the other control has left Standby and returned
to Service. When the Regeneration cycle is complete, the regenerated
unit will enter Standby. Standby on each tank is controlled by the lower
drive output terminals on the NXT circuit board.
Meter input is required on each tank. Unit #1 will begin In Service with
#2, #3, and #4 (if installed) will begin in Standby. At least one unit is
In Service at all times. When flow rate to the Primary Service Unit
increases to a user specified rate, the next unit in sequence will move
from Standby to Service. As the flow rate falls below the user specified
rate subsequent tanks will return to Standby. When the Primary
Service Unit regenerates, the next unit in sequence will become
the new Primary Service Unit. As each units capacity is reached the
controller will initiate a Regeneration of that unit. Depending on the
number of units in the system, and flow rate demand the regenerated
unit will then be placed either into Standby or Service. Only one unit
will be in Regeneration at a time.

Advertisement

Table of Contents
loading

Table of Contents