4.3 Initial Startup
58
GFK-2847R
For public disclosure
You will need the following:
•
Safety Extra Low Voltage (SELV) and Limited Energy Circuit or SELV and Class 2
dc power supply.
•
The power terminal block is supplied with the product. For voltage and requirements,
refer to the Input Power specifications in the table,
•
The mating power terminal block supports stranded 30 to 14 AWG
(0.05 to 2.00 mm
2
) wires. The user calculates proper gauge wiring for current
carrying capacity and loss according to local regulations.
•
At a minimum, the cable must be rated for 75°C (167 °F) or more.
•
USB-compatible keyboard (optional)
•
USB-compatible mouse (optional)
4.3.1 Connecting Input Power
➢ ➢ To connect input power
1.
Verify that the power cable is not energized.
2.
Loosen the screw clamps on the mating power
connector.
3.
Strip the insulation from the power cables.
4.
Secure the power cable to the mating connector,
noting polarity, and tighten the screw clamps. The
torque for the attaching screws is 0.3 Nm (2.66
in-lb).
5.
Apply dc power to the unit. During normal startup
and operation, the QuickPanel
displays as follows:
•
Solid amber while the QuickPanel
up
•
Solid green during normal operation
6.
Once power is applied, the QuickPanel
initializing. The splash screen is the initial display.
➢ ➢ To skip running any programs included in
the StartUp folder: tap Don't run Startup
programs. The Microsoft Windows Embedded
Compact 7 operating system starts automatically.
General
Mounting clamps
FG
+
status LED indicator
+
is starting
+
begins
QuickPanel⁺ Operator Interface User Manual
Specifications.
M2.5
M2
Screw clamps
GND
+24 V dc
Power Connector