226 Actual signals and parameters
All parameters
No.
Name/Value
2205 ACCELER
TIME 2
0.0...1800.0 s
2206 DECELER
TIME 2
0.0...1800.0 s
2207 RAMP SHAPE
2
0.0 = LINEAR
0.1...1000.0 s
2208 EMERG DEC
TIME
0.0...1800.0 s
2209 RAMP INPUT 0 Defines the source for forcing the ramp input to zero.
NOT SEL
DI1
DI2
DI3
DI4
DI5
COMM
Description
Defines the acceleration time 2, ie the time required for the
speed to change from zero to the speed defined by
parameter
2008 MAXIMUM FREQ
MAXIMUM SPEED
(in vector control). The control mode is
selected by parameter
See parameter
2202 ACCELER TIME
Acceleration time 2 is used also as jogging acceleration
time. See parameter
Time
Defines the deceleration time 2, ie the time required for the
speed to change from the value defined by parameter
MAXIMUM FREQ
(in scalar control) /
SPEED
(in vector control) to zero. The control mode is
selected by parameter
See parameter
2203 DECELER TIME
Deceleration time 2 is used also as jogging deceleration
time. See parameter
Time
Selects the shape of the acceleration/deceleration ramp 2.
The function is deactivated during emergency stop.
During jogging, parameter value is set to zero (ie linear
ramp). See
1010 JOGGING
See parameter
2204 RAMP SHAPE
Defines the time within which the drive is stopped if an
emergency stop is activated. See parameter
STOP
SEL.
Time
Not selected
Digital input DI1. 1 = ramp input is forced to zero. Ramp
output will ramp to zero according to the used ramp time.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Fieldbus interface as the source for forcing ramp input to
zero, ie control word
ABB drives profile
5319 EFB PAR 19
word is sent by the fieldbus controller through the fieldbus
adapter or embedded fieldbus (Modbus) to the drive. For
the control word bits, see sections
profile
on page
320
and
on page 315.
(in scalar control) /
9904 MOTOR CTRL
1.
1010 JOGGING
SEL.
2002 MAXIMUM
9904 MOTOR CTRL
1.
1010 JOGGING
SEL.
SEL.
1.
0301 FB CMD WORD 1
bit 6). The control
DCU communication
ABB drives communication profile
Def/FbEq
60.0 s
2002
MODE.
1 = 0.1 s
60.0 s
2008
MODE.
1 = 0.1 s
0.0 =
LINEAR
1 = 0.1 s
1.0 s
2109 EMERG
1 = 0.1 s
NOT SEL
0
1
2
3
4
5
7
bit 13 (with

Hide quick links: