Xmart OPTIMA-RT10-10K User Manual

Ups online double conversion rack / tower installation

Advertisement

Quick Links

www.xmart-ups.com
USER MANUAL - OPTIMA RT10 6K/10K
OPTIMA RT10 6K/10K
UPS ONLINE DOUBLE CONVERSION
RACK / TOWER INSTALLATION
VER.161205-GA2 (ENG)
VER. 1612.05
ENGLISH
USER MANUAL
OPTIMA-RT10-06K-230V
OPTIMA-RT10-10K-230V
ISOTX-06K-OPT-RACK
ISOTX-10K-OPT-RACK
INDEX
1

Advertisement

Table of Contents
loading

Summary of Contents for Xmart OPTIMA-RT10-10K

  • Page 1 INDEX USER MANUAL - OPTIMA RT10 6K/10K VER. 1612.05 ENGLISH USER MANUAL OPTIMA RT10 6K/10K UPS ONLINE DOUBLE CONVERSION RACK / TOWER INSTALLATION OPTIMA-RT10-06K-230V OPTIMA-RT10-10K-230V ISOTX-06K-OPT-RACK ISOTX-10K-OPT-RACK www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 2 XMART is not responsible of mistakes or missing information in this manual.  XMART is not responsible for wrong use a third part can do of this information.  Trademarks and logos in this manual are property of their owners.
  • Page 3: Table Of Contents

    7. UPS CONFIGURATION 8. START-UP INDIVIDUAL UPS PARALLEL UPS 9. ERROR & ALARMS CODES / TROUBLESHOOTING 10. SOFTWARE 11. BATTERIES: MAINTENANCE 12. BATTERIES & CHARGER: CONFIGURATION & SERVICE 13. SUPPORT & WARRANTY 14. REAR PANEL 15. SPECIFICATIONS www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 4 WARNING: Do not connect AC motor based equipment without a careful sizing of the UPS based on inrush current instead of average current. Inrush current typical of motor based system could overload this UPS. WARNING: In case of emergency, power-off UPS and turn it off by <OFF> button in front panel. Then call technical service. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 5 After manufacturing modifications made on this product by user or the use of this product as a part of a system could affect its performance and the compliance of regulations listed in above table. XMART is not responsible of modifications made on this product or its accessories after manufacturing. www.xmart-ups.com...
  • Page 6 In case of installing an optional external ISOTX module, the maximum power of the system will be about 7% lower than max. power of the UPS since part of the power (7% approx.) will be dissipated in the ISOTX. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 7: Safety Instructions

    Inrush current typical of motor based system could overload this UPS. We strongly recommend to place a warning sign on main electrical board to avoid external personnel manipulate AC lines during  revision and start-up work is performed. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 8 This is because a dangerous voltage could be feed by the UPS on the electrical board even AC main service is out of order. Label design should include following information: VOLTAGE BACKFEED RISK UPS CONNECTED TO THIS CIRCUIT Before working on this circuit: * Isolate UPS * Check for dangerous voltage in all circuit terminals. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 9 For Ex models (with external batteries) there must be also DC Circuit Breakers between UPS and battery bank. Some Models include a DC breaker on the rear panel for external battery pack protection; otherwise an external DC Circuit breaker must be installed. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 10 Rack UPS must be installed using L-Shape type guides for supporting UPS weight. Usually this kind of supports is provided with rack cabinets. If not, UPS distributor can provide original XMART telescopic guides as optional accessory. Small black handles included with the UPS are only for locking purposes. UPS cannot be supported only by these handles.
  • Page 11 INDEX USER MANUAL - OPTIMA RT10 6K/10K VERTICAL MOUNTING UPS can be installed in vertical format by using plastic supports (Fig 1 & 2). These supports are included inside the box. 2 MODULES: UPS+XBAT: www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 12 INDEX USER MANUAL - OPTIMA RT10 6K/10K 3 MODULES: UPS+XBART+OPTIONAL ISOTX www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 13 EXTERNAL BATTERY CABINETS (XBAT) – CONNECTION PROCEDURE External batteries must be connected to UPS by using original XMART DC cable provided inside the box, IMPORTANT: All OPTIMA RT 6K and 10K work with 240VDC battery voltage. This voltage is provided by battery packs by connecting 20 batteries 12VDC in series.
  • Page 14 8AWG (10 mm2) 8 AWG (10 mm2) Original XMART Battery modules have their own DC breaker so no external DC breakers are required between UPS and XBAT. 1 TOTAL OUTPUT: 1 x 120Vac (N1*) SEPARE OUTPUTS: 2 x 120Vac (N2*)
  • Page 15 UPS with 220V output generated by UPS inverter. This product has 2 basic modules: UPS & Batteries. This UPS can be feed with 220V-240V line (L-N) to generate one output with a configurable value: 208, 220, 230 or 240Vac. UPS module is connected to XBAT module by using original XMART DC cable. AC TERMINAL BLOCK ON UPS Remove TB cover plate located on rear panel to have access to Terminal Block.
  • Page 16 ISOTX module is an optional accessory not included with the UPS. It provides 2 galvanic isolated outputs 120V each. UPS output is connected to ISOTX input. IMPORTANT: When ISOTX is connected, total power output is decreased in 7% because internal loses in the ISOTX. AC TERMINAL BLOCK CONNECTION BETWEEN UPS AND ISOTX www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 17: Ver.161205-Ga2 (Eng)

    ISOTX outputs can be connected in 3 different configurations according to the needs of the application. IMPORTANT: When 2 x 120V output configuration is selected, each output can only provide 50% of the total UPS output power. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 18: Installation

    UPS will be able to know important information to share the load efficiently. All input and output lines must have their own breakers (one per UPS) for safety reasons and for allowing isolation of any UPS when required. RCCB: Residual Current Circuit Breaker BKR: Magneto-thermic Breaker www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 19 UPS of the parallel system. In battery mode the lack of connection of output neutrals could generate synchronization errors between UPS. In case neutral lines are connected through breakers, there is a possibility of a wrong operation of breakers that forces error states. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 20 UPS of the parallel system. In battery mode the lack of connection of output neutrals could generate synchronization errors between UPS. In case neutral lines are connected through breakers, there is a possibility of a wrong operation of breakers that forces error states. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 21 UPS of the parallel system. In battery mode the lack of connection of output neutrals could generate synchronization errors between UPS. In case neutral lines are connected through breakers, there is a possibility of a wrong operation of breakers that forces error states. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 22 UPS of the parallel system. In battery mode the lack of connection of output neutrals could generate synchronization errors between UPS. In case neutral lines are connected through breakers, there is a possibility of a wrong operation of breakers that forces error states. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 23 CONTROL CABLES: CONNECTION DIAGRAM Parallel system requires all UPS share some important control information by parallel control cables. There are 2 kind of control cables: SHARED CURRENT & PARALLEL CONTROL. They must be connected as indicated in below figure: www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 24: Operation Modes

    BYPASS mode is disable to avoid a not acceptable frequency value at output. 2.- When CF function is activated, maximum power output is de-rated to 60% of maximum nominal capacity. For example, for a 10KVA (8KW) model, when CF is activated maximum output is decreased to 6KVA (4.8KW). www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 25: Ups Configuration

    Verify UPS enters in static bypass mode. Bypass LED must be ON and online LED must be OFF Actuate external bypass switch to OFF state (open). In case of using a XMART MBS, set it to BYPASS position and re-install its safety plate.
  • Page 26 OFF. A- ECO symbol is active on LCD B- Flowchart indicates output is powered from input. ECO MODE A- FC CONVERTER symbol is activated to indicate FC conversion mode is active. FREQUENCY CONVERTER MODE www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 27 INDEX USER MANUAL - OPTIMA RT10 6K/10K A- When a failure is detected, UPS display error code with alert symbol on screen. ERROR/FAILURE MODE www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 28 Some no critical alarms can be muted when this key is selected DOWN When UPS is in configuration mode, this key operates as DOWN () < TEST> < MUTE> CONFIGURATION MODE By pressing these 2 keys at same time, UPS enters in configuration mode. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 29 (2) + (3) : Alarm/error code (2) : Menu ID (in CONFIGURATION mode) (4) : Not used in this model (5) : Battery fault active (6) : Battery low level (7) : Output Overload detected (8) : Output short-circuit detected www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 30 Supplied Power is between 76 - 100% BATTERY LEVEL METER It shows by a 4 segments bar the charge level of batteries: 25%: Between 0 - 25% 50%: Between 26 - 50% 75%: Between 51 - 75% 100%: Between 76 - 100% www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 31: Start-Up

    ● No batteries start-up function ● ● ● ● ● ● Battery voltaje setting ● ● ● ● ● ● Battery charger setting ● ● ● Inverter setting ● ● ● UPS output setting ● Function available. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 32 - Valid input FREQUENCY range for bypass mode can be configured by setting high limit and low limit: PAR 03: sets high limit (in Hz) PAR 02: sets low limit (in Hz) ECO ENABLE / DISABLE: ENA : ENABLE DIS : DISABLE www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 33 NOT USED IN THIS MODEL NOT USED IN THIS MODEL NO BATTERIES START-UP: Enable/Disable YES: Allowed NO: Not allowed BATTERY VOLTAGE SETTING: ** ONLY FOR TECHNICAL SERVICE ** ADD: Increase SUB: Decrease Set values with keys:  &  www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 34 Not Allowed (No permitido) Allowed (permitido) Output Voltage (Voltaje de salida) AUDIBLE ALARMS BEEPS ERROR/FAILURE: Continuously BATTERY MODE: 1 "Beep" / 4 seconds BYPASS MODE: 1 "Beep" / 2 minutes 1 "Beep" / 1 second. LOW BATTERY: www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 35 NOTE 1: If any error or warning message is indicated in LCD, please revise Troubleshooting section of this manual. NOTE 2: UPS batteries maybe are not fully charged. UPS could require about 4 to 6 hours to recharge batteries up to 100% of their capacity. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 36 13.- Before closing external AC output breakers to connect AC outputs in parallel, it is mandatory to measure output voltage of each UPS to confirm all of them are similar. Measure with a digital voltmeter. Maximum acceptable difference is about 1.5Vac. If difference is above 1.5Vac technician must adjust output by modifying function 16 of configuration menu. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 37 NOTE: If you disconnect parallel control cables in any of the operative UPS of the system, a communication problem will occur and the parallel system will be shut down. At this moment selected UPS is currently powered off and isolated so that it can be serviced or simply removed. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 38 Some errors and alarms could block UPS until problem is solved and UPS unblocked by operator. Operator must be sure cause of problem has been solved before clear alarm and unblock UPS. Alarm can be deleted by pressing <UP> and <DOWN> keys at same time, when UPS is in BYPASS mode. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 39 NEGATIVE OUTPUT: External device is injecting current to the UPS from its output. SHORT CIRCUIT detected at Battery charger BATTERY PROBLEM Start-up RECTIFIER PROBLEM in Battery mode DC BUS PROBLEM: Fast voltage variations detected at DC Bus. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 40 UPS output by mistake. IMPORTANT: In case of extreme failure or when burning smell is detected, UPS input lines must be powered off immediately and UPS must be turned-off by <OFF> button. Wait until LCD turns-off. Then call technical service. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 41: Software

    It is configured on charger board. Identify jumpers 06, 07 & 08 to set them according to following table: JUMPERS CHARGER BOARD JP06 CHARGER OPEN OPEN CONNECTED OPEN JP07 CHARGER OPEN CONNECTED OPEN OPEN JP08 CHARGER CONNECTED OPEN OPEN OPEN www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 42: Support & Warranty

    - In no event will XMART be liable for any damages caused by the product or the failure of the product to perform, including any lost profits or savings or special, incidental, or consequential damages.
  • Page 43: Rear Panel

    12 FAN: ISOTX (optional module) 6 Intelligent port 13 AC Input: ISOTX (optional module) 7 USB & RS232 14 AC Output: ISOTX (optional module) RS232 COMMUNICATION PORT Serial communication port – Pinout: Pin 2: RX Pin 3: TX Pin 5: GND www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 44: Specifications

    4 H (90%) Additional packs / Paquetes adicionales Depending on external battery configuration (depende de cantidad de baterías adicionales) Charging Amps / Corriente de Carga 1A, 2A, 3A & 4A (configurable) Charging Voltage / Voltaje Cargador 273.0 VDC www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 45: Ver.161205-Ga2 (Eng)

    Note 3: If installed over 1.000m altitude, output power is derated 1%/100m over 1.000m. La salida se reduce en 1% cada 100m, sobre los 1.000msnm. Note 4: Bypass mode is prohibited automatically when CF function is activated. El modo bypass se anula automaticamente cuando se activa la función CF. www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 46: Ver.161205-Ga2 (Eng)

    INDEX USER MANUAL - OPTIMA RT10 6K/10K NOTAS www.xmart-ups.com VER.161205-GA2 (ENG)
  • Page 48 USA Headquarters: EUROPE Headquarters: Latin America Headquarters: 10540 NW 26th St, Ave. Can Bordoll 60, Nave 4. Zona Ind. San Vicente II, C/ F, A11 Doral, FL 33172. USA Sabadell 08202. Spain Maracay. Venezuela...