USER MANUAL - OPTIMA-33 10K / 20K / 30K 1. GENERAL SAFETY INSTRUCTIONS WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults.
Page 4
USER MANUAL - OPTIMA-33 10K / 20K / 30K WARNING: EQUIPMENT DISPOSAL Out of service units : It is strongly recommended to dispose this piece of equipment according to valid directives in your country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials to be recycled.
If external batteries are required for 230/120V models or for extending runtime, EXBATT external batteries can be connected directly to the UPS. EXBATT-33-T10K: EXBATT for OPTIMA-33 10K. Includes 20 batteries 12V/9AH with DC breaker 50Amps. DC voltage: 240Vdc (nominal). EXBATT-33-T20K: EXBATT for OPTIMA-33 20K.
Page 6
USER MANUAL - OPTIMA-33 10K / 20K / 30K REAR PANEL 1.- RS232 7.- FAN for power stage / Ventilación Forzada etapa de potencia 2.- USB 8.- EXBATT connector / Conector Baterías Externas 3.- EPO (Emergency Stop / Parada Emergencia) 9.- AC Input Breaker / Breaker de Entrada AC...
Page 7
USER MANUAL - OPTIMA-33 10K / 20K / 30K 3.- UPS INSTALLATION: SITE PLANNING SAFETY INSTRUCTIONS WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL SAFETY INSTRUCTIONS”. WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION REACH AND LIABILITY LIMITATION: The preparation of the site, wiring and all protection devices must be supplied by end user and it will not be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up.
Page 8
USER MANUAL - OPTIMA-33 10K / 20K / 30K SITE INSPECTION AND INSTALLATION CONDITIONS REGULATIONS AND LEGAL DIRECTIVES It is necessary to check that installation site, wiring and power protection in the installation supplied by end user, fulfill technical parameters required by UPS.
Page 9
USER MANUAL - OPTIMA-33 10K / 20K / 30K TOWER UPS INSTALLATION SITE CONSIDERATIONS * This product has been designed to be used indoors, protected from water, direct sun light, dust and extreme temperature. * Install the UPS in well ventilated location or air conditioned room. Temperature must be always in acceptable range according to technical specifications table of this manual.
Page 10
USER MANUAL - OPTIMA-33 10K / 20K / 30K CIRCUIT BREAKERS AND WIRING SELECTION Breakers and Gauge of the wires used in the installation must be rated to drive current values in Amps as indicated in below tables. NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than suggested values in this section, please follow local regulations.
Page 11
USER MANUAL - OPTIMA-33 10K / 20K / 30K 208/120VAC INPUT OUTPUT EXT. BATT Breaker: 63 Amps AC (Curve D) Breaker: 63 Amps AC (Curve D) Breaker: 50 Amps DC (Curve C) Max. Nominal Current (Ph-N): Max. Nominal Current (Ph-N):...
USER MANUAL - OPTIMA-33 10K / 20K / 30K 4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK AC LINES CONNECTION PROCEDURE • Make sure the UPS is Off before starting the installation. • Remember to check all wires to be connected are not powered (including external batteries).
Page 13
USER MANUAL - OPTIMA-33 10K / 20K / 30K EXTERNAL BATTERY CABINETS – CONNECTION PROCEDURE UPS Tower type WARNING Make sure EXBATT model to be connected is compatible with UPS model. For OPTIMA-33 models, battery pack voltage is 240Vdc. Measure and verify DC voltage supplied by battery pack before making connections.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 5.- UPS INSTALLATION: PARALLEL UPS - TERMINAL BLOCK GENERAL COMMENTS FOR PARALLEL SYSTEMS * Parallel Installation allow up to 3 units in parallel. * All units must have similar control board firmware version. If all UPS belong to same manufacturing batch, firmware will be the same. If units below to different manufacturing batches, please contact your distributor to ask about compatibility to connect in parallel.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 6.- START-UP: SINGLE UPS INSPECTION BEFORE START UP Make sure all wires are tightly connected to terminal block. Any loose connection will produce overheating, failures and damage to UPS. Make sure all instructions of sections 3 and 4 have been performed correctly.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 7.- START-UP: PARALLEL UPS REQUIREMENTS FOR PARALLEL SYSTEM WARNING: Before starting up this parallel UPS system is mandatory to comply with all below requirements. 1.- Maximum quantity of UPS to be connected in parallel is 3. Do not try to connect more than 3 units in parallel.
Page 19
USER MANUAL - OPTIMA-33 10K / 20K / 30K START UP FOR PARALLEL UPS SYSTEM WARNING: Make sure all requirements and previous inspection have been revised and complied before initiating start up procedure. If not please do not try to continue with start-up procedure.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 8.- OPERATION INTERFACE UPS FRONT PANEL: PUSH BUTTON TOWER FRONT PANEL ON / ENTER POWER ON : Keep selected during 1 second to power UPS ON. ENTER : It Works as “ENTER” or confirmation function when LCD is in configuration menu mode.
Page 21
USER MANUAL - OPTIMA-33 10K / 20K / 30K UPS FRONT PANEL: LED INDICATOR LIGHTS There are 4 LED indication lights in front panel, located below LCD. These 4 LEDs describe UPS condition as follow: MODE Bypass Line Battery Fault ●...
Page 22
USER MANUAL - OPTIMA-33 10K / 20K / 30K UPS FRONT PANEL: LCD This UPS has a sophisticated LCD able to display all important information related to input line, UPS status and values, operation mode and error and alarm messages. It is a powerful information tool to know what is happening at any moment.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 9.- OPERATION: SINGLE UPS This is a True On Line Double Conversion UPS and it is designed to offer clean, bump-less and highest quality power to your computer related equipments protecting also your valuable data. Power delivered by UPS is 100% sine wave as main line.
Page 24
USER MANUAL - OPTIMA-33 10K / 20K / 30K FUNCTION DISPLAY ACCORDING TO OPERATION MODE In each mode UPS will show some different alternating screens as described below: Operating mode/status When UPS is powered on, it will enter into this mode for a few seconds as initializing the CPU and...
Page 25
USER MANUAL - OPTIMA-33 10K / 20K / 30K When the input voltage is within acceptable range, UPS will provide pure and stable AC power to AC mode Description output. The UPS will also charge the battery at AC mode.
Page 26
USER MANUAL - OPTIMA-33 10K / 20K / 30K When the output frequency is set to “CF”, the inverter will output constant frequency (50 Hz or 60 CVCF mode Description Hz). At this mode, the UPS will have no bypass output but still charge battery.
Page 27
USER MANUAL - OPTIMA-33 10K / 20K / 30K When input voltage is within acceptable range and bypass is enabled, turn off the UPS and it will enter Bypass mode Description Bypass mode. Alarm beeps every two minutes. LCD display When UPS is in AC mode or CVCF mode, press “Test”...
Page 28
USER MANUAL - OPTIMA-33 10K / 20K / 30K If some errors occur in the UPS (but it is still running normally), it will show one more screen to Warning status Description represent the warning situation. In the warning screen, the icon will be flashing, and it can show up to 3 error codes and each code indicates one error.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 10.- OPERATION: PARALLEL UPS UPS operation modes for UPS in parallel are basically same than described for single UPS. However it is important to remark all UPS in parallel system must work under same mode at same time. Parallel function does not allow different operation modes between UPS of the system.
Page 30
USER MANUAL - OPTIMA-33 10K / 20K / 30K 11.- UPS CONFIGURATION Parameter 1 Parameter 2 Parameter 3 * This menu is activated by simultaneous selection of “Test/Up” + “Mute/Down” keys during 1 second when UPS is in BYPASS mode.
Page 31
USER MANUAL - OPTIMA-33 10K / 20K / 30K Configuration menu texts TEXT DESCRIPTION Enable Disable Auto Battery Normal mode (not CVCF mode) CVCF mode Subtract Not allowed Allow Reserved N.L. Neutral line loss Check OP.V Output voltage Parallel, 001 means the first UPS...
Page 32
USER MANUAL - OPTIMA-33 10K / 20K / 30K 01: Output voltage Interface Setting Parameter 3: Output voltage You may choose the following output voltage in parameter 3: 208: Presents output voltage is 208Vac 220: Presents output voltage is 220Vac...
Page 33
USER MANUAL - OPTIMA-33 10K / 20K / 30K 04: Frequency range for bypass Interface Setting Parameter 2: Set the acceptable low frequency for bypass. 50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
Page 34
USER MANUAL - OPTIMA-33 10K / 20K / 30K 09: Maximum battery discharge time setting Interface Setting Parameter 3: 000~999: Set the maximum discharge time from 0 min to 999 min. UPS will shut down to protect battery if the discharge time arrives before the battery is under voltage. The default value is 990 min.
Page 35
USER MANUAL - OPTIMA-33 10K / 20K / 30K 13: Battery voltage calibration Interface Setting Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to real figure. Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
Page 36
USER MANUAL - OPTIMA-33 10K / 20K / 30K 18: Output A voltage calibration Interface Setting Parameter 2: it always shows OP.V as output voltage. Parameter 3: it shows the internal measurement value of the output A voltage, and you can calibrate it by pressing Up or Down according to the measurement from an external voltage meter.
USER MANUAL - OPTIMA-33 10K / 20K / 30K 12.- ERROR CODES, ALARMS & TROUBLESHOOTING ERROR / FAILURE CODES ON LCD When a failure or alarm is detected by the UPS, an alarm or error code is presented in front panel LCD. This code or symbol will allow to identify the problem.
Page 38
USER MANUAL - OPTIMA-33 10K / 20K / 30K ALARM CODES ON LCD WARNING WARNING CODE DESCRIPTION Battery unconnected Input Neutral loss Input Phase Abnormal Battery over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure L1 Input fuse broken...
Page 39
USER MANUAL - OPTIMA-33 10K / 20K / 30K ALARM SYMBOLS ON LCD Warning Icon (flashing) Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second...
USER MANUAL - OPTIMA-33 10K / 20K / 30K TROUBLESHOOTING PROBLEM DESCRIPTION PROBABLE ROOT CAUSE SUGGESTED ACTION Input power cord is not connected Check input power cord connection. * LCD does not show input voltage value * AC input failure alarm active Input power cord is connected into UPS outlet.