3.1 Introduction
You should read all the sections in Basic Installation.
It is important that the correct steps are followed when installing the NextMove e100.
This section describes the mechanical installation of the NextMove e100.

3.1.1 Location requirements

You must read and understand this section before beginning the installation.
To prevent equipment damage, be certain that input and output signals are
i
powered and referenced correctly.
NOTICE
To ensure reliable performance of this equipment be certain that all signals to/
i
from the NextMove e100 are shielded correctly.
NOTICE
Avoid locating the NextMove e100 immediately above or beside heat generating
i
equipment, or directly below water steam pipes.
NOTICE
Avoid locating the NextMove e100 in the vicinity of corrosive substances or
i
vapors, metal particles and dust.
NOTICE
The safe operation of this equipment depends upon its use in the appropriate environment.
The following points must be considered:
The NextMove e100 is designed to be mounted indoors, permanently fixed and located.
The NextMove e100 must be secured by the slots in the metal base.
The NextMove e100 must be installed in an ambient temperature of 0 °C to 45 °C (32 °F
to 113 °F).
The NextMove e100 must be installed in relative humidity levels of less than 80% for
temperatures up to 31 °C (87 °F) decreasing linearly to 50% relative humidity at 45 °C
(113 °F), non-condensing.
The NextMove e100 must be installed where the pollution degree according to
IEC 60664-1 shall not exceed 2.
There shall not be abnormal levels of nuclear radiation or X-rays.
MN1941WEN

Basic Installation

3 Basic Installation
Basic Installation 3-1