Section 6.1.6

Other Approvals

This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section 6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS910 has passed the following Electromagnetic Compatibility (EMC) and environmental tests.
EMC Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
Other Approvals
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Signal Ports
± 4 kV Line-to-Ground
DC Power Ports
± 2 kV Line-to-Ground
AC Power Ports
± 4 kV Line-to-Ground
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
± 2 kV Line-to-Line
± 1 kV Line-to-Line
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m Continuous
Chapter 6
Certification
Severity Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
31