Adjustments Before First Firing (Light-Oil Operation) - Riello RLS 70 Installation Instruction

Table of Contents

Advertisement

Refit the burner to the slide bars 3) (Fig. 13) at approximately 4"
from the sleeve 4) - burner positioned as shown in (Fig. 7, page 12)
- insert the ignition electrode cables and then slide the burner up to
the sleeve so that it is positioned as shown in (Fig. 13).
Refit screws 2) (Fig. 13) on slide bars 3).
Secure the burner to the sleeve by tightening screws 1).
Connect the oil pipes again by screwing on the two connectors 6)
(Fig. 7, page 12).
When fitting the burner on the two slide bars, it is
advisable to gently draw out the high tension cables
until they are slightly stretched.
WARNING
4.7

Adjustments before first firing (light-oil operation)

• Combustion head setting
The setting of the combustion head depends exclusively on the
maximum delivery of the burner.
Turn screw 5) (Fig. 14) until the notch shown in diagram (Fig. 15)
is level with the front surface of flange 6) (Fig. 14).
Example: Burner RLS 100
maximum burner delivery = 23.1 GPH.
If diagram (Fig. 15) is consulted it is clear that for this delivery, the
combustion head must be adjusted using notch 3, as shown in
(Fig. 14).
N° Notches
Maximum fuel oil delivery USGPH
NOTE:
In case of high altitude installation site, head setting must re-
fer to the "corrected capacity" according procedure descript-
ed at page 10.
6046
Installation
• Pump adjustment
No settings are required for the pump, which is set to 174 PSI by
the manufacturer. This pressure must be checked and adjusted (if
required) after the burner has been ignited.
The only operation required in this phase is the application of a
pressure gauge on the appropriate pump attachment.
• Air damper adjustment
The first time the burner is fired leave the factory setting unchanged
for both low and high fire operation.
• Ignition pilot adjustment
Place the pilot and electrode as shown in (Fig. 16).
The pilot works correctly at pressures ranging from 6 - 12" WC.
D1149
Fig. 14
D2304
Fig. 15
14
D2591
1/32"
To set the pilot without main burner operation, pro-
ceed as follows:
Move the jumper from terminals "30-V11" to
WARNING
terminals "30-VP", as given in (Fig. 17), this
way the main valve will not be energized.
With the burner in the manual position, hold the
air damper in the minimum position and make
the setting.
When the setting is correct, replace the jumper
on "30-V11".
D2317
D2305
Fig. 13
Ignition pilot
Electrode
Fig. 16
MB - Burner terminal strip
Fig. 17