Generac Power Systems 8 kVA Owner's Manual page 34

Air-cooled generators
Hide thumbs Also See for 8 kVA:
Table of Contents

Advertisement

Quick Reference Guide
Active Alarm
LED
UNDERSPEED
RED
STEPPER
RED
OVERCURRENT
MISWIRE
RED
OVERVOLTAGE
RED
LOW BATTERY
YELLOW
BATTERY
YELLOW
PROBLEM
CHARGER
YELLOW
WARNING
SERVICE A
YELLOW
SERVICE B
YELLOW
INSPECT BATTERY
YELLOW
36
Table 6-1. System Diagnosis (Continued)
Problem
Unit will not start in
AUTO with utility loss.
Unit will not start in
AUTO with utility loss.
Unit will not start in
AUTO with utility loss.
Unit will not start in
AUTO with utility loss.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Things to Check
Check the LED's /
Contact an IASD.
Screen for alarms.
Check the LED's /
Contact an IASD.
Screen for alarms.
Check the LED's /
Contact an IASD.
Screen for alarms.
Check the LED's /
Contact an IASD.
Screen for alarms.
Clear alarm. Using the control panel, check
the battery by navigating to the BATTERY
Check the screen for
MENU option from the MAIN MENU. If it
states battery is GOOD, contact an IASD.
If it states CHECK BATTERY, replace the
battery.
Check the screen for
Contact an IASD.
Check the screen for
Contact an IASD.
Check the screen for
Perform SERVICE A maintenance. Press
ENTER to clear.
Check the screen for
Perform SERVICE B maintenance. Press
ENTER to clear.
Check the screen for
Inspect Battery. Press ENTER to clear.
Owner's Manual for 50 Hz Air-Cooled Generators