Service Manual
(7)Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor
unit)
Mainly detect:
Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken
Fault diagnosis process:
Start
Check wiring of the
reactor (L) of the
outdoor unit and the
PFC capacitor
Whether there is any
damage or
short-circuit?
Disconnect the terminals for the
reactor and measure the resistance
between the two terminals of the
reactor by an ohm gauge
Whether there is any damage
or short-circuit?
Replace the control
panel AP1
End
Installation and Maintenance
Y
N
Replace the reactor
Y
N
Replace it as per the
wiring diagram and
reconnect the wires
N
Restart the unit
N
If the fault is eliminated?
If the fault is eliminated?
Y
Y
55