Connecting accessories 11 Technical data 6 Commissioning and adjusting Dimensions and setting-out coordinates Preparations Sound pressure levels Filling and venting the heating medium sys- Technical specifications Electrical circuit diagram Balance temperature Item register Stop temperature NIBE F2300 Table of Contents |...
F2300 is CE marked and fulfils IP24. Do not run the unit with removed panels or protection. The CE marking means that NIBE ensures that the product Touching rotating equipment, hot surfaces or high voltage parts meets all regulations that are placed on it based on relev- can cause personal injury due to entrapment, burns or electric shocks.
Page 5
Insects and small animals can enter the electronic parts and cause damage and fire. Instruct the user to keep the surrounding equip- ment clean. Take care when carrying the unit by hand. NIBE™ F2300 Chapter 1 | Important information...
Caution Always give the product's serial number when reporting a fault. Country specific information Installer manual This installer manual must be left with the customer. Chapter 1 | Important information NIBE™ F2300...
(see page Care must be exercised so that the heat pump is not scratched during installation. Do not place F2300 directly on the lawn or other non solid surface. NIBE™ F2300...
Page 10
If F2300 must be transported across soft ground, for ex- ample a lawn, we recommend that a crane that can lift it to the set up location is used. When the F2300 is lifted Caution by crane the packaging must be untouched and the load If none of the recommended alternatives is used equally distributed with a boom, as illustrated above.
Page 11
If the house has a cellar the caisson must be positioned Route the pipe downward from F2300. so that it does not affect the house. Otherwise the caisson The condensation water pipe must have a water trap to can be positioned directly under the heat pump.
Installation area The distance between F2300 and the house wall must be at least 400 mm. Clearance above the F2300 should be at least one metre. Fritt utrymme bakom 600 mm Min. avstånd vid användning av flera F2300 Fritt utrymme framför...
3 The heat pump design General Chapter 3 | The heat pump design NIBE™ F2300...
Page 15
Pipe connections XL 1 Connection, heating medium out of F2300, G1 1/4” (Ø35mm) XL 2 Connection, heating medium in to F2300, G1 1/4” (Ø35mm) XL 20 Service connection, high pressure XL 21 Service connection, low pressure XL 40 Connection, drip tray drain...
Pipe installation must be carried out in accordance with Pressure drop, heating medium current norms and directives. F2300 can only operate up to a return temperature of side about 55 °C and an outgoing temperature of about 65 °C from the heat pump.
Docking alternatives F2300 can be installed in several different ways, for ex- ample with integrated or external control. The safety equipment must be installed in accordance with current regulations for all docking options. See for more docking options. When docking with F2300 a minimum available system volume of at least 20 litres per kW output on the heat pump is recommended.
Charge pump for F2300 can be connected to separate supply or to terminal block (X3). NOTE! If F2300 is not powered and the charge pump is connected to the terminal block (X3) there is a risk of freezing A common alarm can be connected to terminal (X4).
Incoming supply cable is supplied and factory connected to the terminal block -X1. Approx. 1.8 m cable is access- ible outside the heat pump. On installation the unions must be mounted on the rear of the heat pump. Chapter 5 | Electrical connections NIBE™ F2300...
X5:2 (compressor blocking) to prevent MP alarm. External heating cable (KVR 10) F2300 is equipped with a terminal block for an external heating cable (EB14, not supplied). The connection is fused with 250 mA (F3, 15 W/m). If another cable is to be used the fuse must be changed to the appropriate size.
A5, see the section "Control - Channel descrip- trough on the outside of F2300. The transfer from elec- tion". trical cable to heating cable must occur after the lead-in External additional heat is connected via the additional to the condensation water trough.
12 – 230V Hjälpkontaktor External indication of main alarm F2300 is equipped with a contact for external indication of common alarms. The function becomes active with all types of existing alarms. Max load on the relay contact is250V 2A.
1. The heating medium system is filled with water to the required pressure. F2300 is equipped with a collar heater that heats the fan 2. Vent the system using the venting nipple on the en- collar when necessary (not activated on delivery).
AA21:J2) or thermostat, terminal block (X5) must not be connected. 2. Turn the isolator switch on. 3. Ensure that the F2300 is connected to the power source. 4. Check that the motor protection (FC2) is on. 5. Check that the LED on phase sequence sensor (BA1) lights red.
10%. The temperature difference shall be as in the diagram below (+1- 2 K). At outdoor temperatures above 28 °C F2300-14 F2300-20 Chapter 6 | Commissioning and adjusting NIBE™ F2300...
Plus button not need to have access to the controller. The plus button (S1) is used to browse through F2300 has an integrated return line sensor that limits the the channel system (forwards) or raise the value return temperature. of the selected parameter.
Shows the current channel. Change channels using the Fan on, low speed Plus button or the Minus button. Fan on, high speed Value: 01 Shows the current value. Increase/decrease value using the plus button respective minus button. Chapter 7 | Control - Introduction NIBE™ F2300...
60 minutes falls below channel A7 + 2.1 °C the counter is reset. It does not start counting again unless the temperature is sufficiently high once again. utelufttemp. Utelufttemperatur NIBE™ F2300 Chapter 7 | Control - Introduction...
After two minutes the com- pressor starts again (if the pressure has fallen), other- wise there is a constant high pressure alarm (alarm 06). 5. The temperature on the flow temperature sensor falls below 4 °C. Chapter 7 | Control - Introduction NIBE™ F2300...
(1 – 9) for communication with the indoor module. Compressor on. For example 3 x F2300 in the same system are allocated Compressor blocked due to an alarm the addresses 1, 2 and 3. The F2300 that produces hot Compressor start in nn minutes.
Page 32
1 and 120 minutes. Factory setting 120 minutes. Stop temperature, the set ambient temperature value when the downtime relay is activated, F2300 stops. When the stop temperature is set between 0 and -20 °C the flow temperature is limited linearly to -10 °C / 65 °C to -20 °C / 63 °C (see diagram on page 39).
See the manual for the indoor module. NOTE High room temperature As F2300 can be connected to a large number External switch for changing the room heating activ- of external units, these should also be checked. ated.
Page 34
Check the connection difference for the thermo- stat. Check the start temperature hot water in any NIBE indoor module. Check the charge flow and the particle filter which may be partially clogged. Hot gas temperature exceeds 135 °C. Indicated as 17 in channel S1.
11 Technical data Dimensions and setting-out coordinates 1345 1455 Fritt utrymme bakom 600 mm Min. avstånd vid användning av flera F2300 Fritt utrymme framför Chapter 11 | Technical data NIBE™ F2300...
The sound pressure levels are further affected by walls, Sound pressure levels bricks, differences in ground level, etc and should there- F2300 is usually placed next to a house wall, which gives fore only be seen as guide values. a directed sound distribution that should be considered.
Min/Max air temp °C -25/40 Defrosting system hot gas defrosting Heating medium Min/Max system pressure heating medium 0.05/0.3 (0.5/3 bar) Min/Max flow 0.33/0.67 0.47/0.94 Nominal flow 0.33 0.47 Internal pressure drop at nominal flow Chapter 11 | Technical data NIBE™ F2300...
Page 41
Nominal flow corresponding DT=10 K at 7/45. Working area During shorter time it is allowed to have lower working temperatures on the water side, e.g. during start up. NIBE™ F2300 Chapter 11 | Technical data...