ECR International G95V Installation Manual And Operating Instructions page 31

Natural and propane gas two stage high efficiency (condensing) warm air furnace
Table of Contents

Advertisement

FIGURE 24 - HORIZONTAL RIGHT VENT AND DRAINING OPTION
1.
Connect two (2) 2" Street elbows (in parts bag) to the coupler on the exhauster
(Add 2" nipple for 120K BTU units). Ensure exhauster coupler drain outlet is
facing downward 15°.
2.
Remove 2.5" knockout and connect 2" vent pipe (field supplied). If using 1.5"
or 3" vent, make transition as close as possible to the unit and on a vertical
section.
3.
Install gasket on panel then vent bracket, use three (3) self tapping screws
(all parts from parts bag). If using 1.5" or 3" vent, make transition as close as
possible to the unit and on a vertical section.
4.
Remove 2.5" knockout and connect 2" air intake coupler with gasket on the
outside of unit, use the 2" nut to fasten this (all parts from parts bag). **Refer to
page 26 for inducer orientation**
5.
Connect 2" street elbow (from parts bag) and intake pipe (field supplied). If
using 1.5" or 3" intake, make transition as close as possible to the unit and on
a vertical section.
1.
Remove 2.5" knockout and connect 2" nipple approximately 7" long (field
supplied) to the coupler on the exhauster. Ensure exhauster coupler outlet is
facing right side approximately 15°.
2.
Connect 2" elbow and 2" vent pipe (field supplied).
3.
Install gasket on panel then vent bracket, use three (3) self tapping screws
(all parts from parts bag). If using 1.5" or 3" vent, make transition as close as
possible to the unit and on a vertical section.
4.
Remove 2.5" knockout and connect 2" air intake coupler with gasket on the
outside of unit, use the 2" nut to fasten this (all parts from parts bag). **Refer to
page 26 for inducer orientation**
5.
Connect 2" street elbow (from parts bag) and intake pipe (field supplied). If
using 1.5" or 3" intake, make transition as close as possible to the unit and on
a vertical section.
Instructions for Horizontal Right with Right Side Venting
6.
Remove two (2) 7/8" knockouts and install the condensate trap bracket by
removing and reusing the 2 top panel screws, install condensate trap with
gasket, hold in place with 2 screws (all parts supplied in parts bag).
7.
**IMPORTANT** Connect a 1/2" tee fitting (field supplied) to the outlet of the
condensate trap.
8.
Connect 1/2" drain tube (field supplied) and route to floor drain or condensate
pump.
9.
Connect one end of the 5/8" tubing (in parts bag) to the drain on the front
manifold cover, route to the larger outlet on the condensate trap, cut excess
tube and hold in place with supplied hose clamps. Tubing should slope towards
drain trap with no sags.
10. Connect one end of the 1/2" tubing (in parts bag) to the lower drain outlet on
the exhauster coupling, route to the smaller inlet on the condensate trap, cut
excess tube and hold in place with supplied hose clamps. Tubing should slope
towards drain trap with no sags.
Instructions for Horizontal Right with Top Venting
6.
Remove two (2) 7/8" knockouts and install the condensate trap bracket by
removing and reusing the 2 top panel screws, install condensate trap with
gasket, hold in place with 2 screws (all parts supplied in parts bag).
7.
**IMPORTANT** Connect a 1/2" tee fitting (field supplied) to the outlet of the
condensate trap.
8.
Connect 1/2" drain tube (field supplied) and route to floor drain or condensate
pump.
9.
Connect one end of the 5/8" tubing (in parts bag) to the drain on the front
manifold cover, route to the larger outlet on the condensate trap, cut excess
tube and hold in place with supplied hose clamps. Tubing should slope towards
drain trap with no sags.
10. Connect one end of the 1/2" tubing (in parts bag) to the lower drain outlet on
the exhauster coupler, route to the smaller inlet on the condensate trap, cut
excess tube and hold in place with supplied hose clamps. Tubing should slope
towards drain trap with no sags.