Figure 3-5 Dip Switches Sw1-A And Sw2-B - Siemens SITRANS F Hardware Installation Instructions

Ultrasonic flowmeter clamp-on communications module
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

RS-485 Connector J1
DIP Switch Settings - SW1 (A) & SW2 (B)
Figure 3-5
Address Selection: A1-A6
These switches enable setting of the physical address on the RS485 network.
Switch Code: A1=1, A2=2, A3=4, A4=8, A5=16, A6=32
For example, to set address to equal 44 set switches to:
A1 Off, A2 Off, A3 On, A4 On, A5 Off, A6 On
Baud Rate Selection: A7-A8
9600
19200 A7 ON A8 OFF
38400 A7 OFF A8 ON
76800 A7 ON A8 ON
Profile Selection: B1-B6
See selection table 3-1.
Protocol Selection: B7-B8
Modbus RTU/Modbus TCP/IP B7 OFF B8 OFF
BACnet IP/BACnet MSTP
Ethernet /IP
N2 Metasys
SITRANS F US Clamp-on Communications Module
Hardware Installation Instructions, 03/2015, A5E32586525-AE
Pin
Signal
J1-1
RS-485+
J1-2
RS-485-
J1-3
RS-485 GND
J1-4
N/A
J1-5
N/A
J1-6
N/A
DIP Switches SW1-A and SW2-B
A7 OFF A8 OFF
B7 ON
B7 OFF B8 ON
B7 ON
F US Clamp-on Communications Module Kit Installation
Description
Signal +
Signal -
Ground
No Connection
No Connection
No Connection
B8 OFF19200
B8 ON
15