Specifications
I/O Power Supply Unit
Item
Input Voltage
Allowable Input Voltage Range
Input Current
Output Capacity
Dimensions
Weight
Power Indicator
Lights when power
is supplied.
Power
Supply
System
Control
Circuit
Power
Detection
Circuit
CV500-IPS01
100 through 120 VAC/200 through 240 VAC 50/60 Hz
85 to 132 VAC/170 to 264 VAC
160 VA max.
2 A, 24 VDC
34.5 x 250 x 116 mm (WxHxD)
700 grams max.
AC Power Source
Supply a voltage of 100 to 120 VAC
or 200 to 240 VAC
24 VDC Output
Use these terminals to supply power to the
DC Input Units. These terminals can supply a
current of up to 2 A. If a current higher than 2
A is required, add a number of I/O Power
Supply Units or use a separate power supply.
Since the PC assumes a current exceeding 2
A from these terminals is a battery error, it ter-
minates the output these terminals.
Power ON Output
These terminals are internally short-circuited
while power is ON (24 VDC output). The maxi-
mum switching capacity of the terminals are as
follows: 2 A, 250 VAC (cos = 1) 0.5 A, 250
VAC (cos = 1) 2 A, 24 VDC
Appendix B