2. ELECTRICAL DATA

2.1. Heat pump type
Rating Conditions (ISO T1)
Indoor·······220V 50Hz Single phase
Outdoor····220V 50Hz Singel phase / 380V 50Hz 3 phase
Service
Indoor unit
Ref.
Outdoor unit
Mode
Capacity (W)
Total Input (kW) (In + Out)
Input (kW)
Current (A)
Current (A)
Starting current (A)
Indoor·······230V 50Hz Single phase
Outdoor····230V 50Hz Singel phase / 400V 50Hz 3 phase
Service
Indoor unit
Ref.
Outdoor unit
Mode
Capacity (W)
Total Input (kW) (In + Out)
Input (kW)
Current (A)
Current (A)
Starting current (A)
Indoor·······240V 50Hz Single phase
Outdoor····240V 50Hz Singel phase / 415V 50Hz 3 phase
Service
Indoor unit
Ref.
Outdoor unit
Mode
Capacity (W)
Total Input (kW) (In + Out)
Input (kW)
Current (A)
Current (A)
Starting current (A)
PCA-P3HA
PUH-P3VGAA
.UK
1
Cooling
Heating
7,500
9,200
3.36
3.41
0.09
0.09
0.44
0.44
15.31
15.54
85
85
PCA-P3HA
PUH-P3VGAA
.UK
1
Cooling
Heating
7,500
9,200
3.36
3.41
0.09
0.09
0.43
0.43
14.63
14.85
89
89
PCA-P3HA
PUH-P3VGAA
.UK
1
Cooling
Heating
7,500
9,200
3.36
3.41
0.09
0.09
0.41
0.41
14.02
14.24
93
93
PUH-P3YGAA
.UK
1
Cooling
Heating
7,500
9,200
3.36
3.41
0.09
0.09
0.44
0.44
5.23
5.32
43
43
PUH-P3YGAA
.UK
1
Cooling
Heating
7,500
9,200
3.36
3.41
0.09
0.09
0.43
0.43
4.96
5.04
45
45
PUH-P3YGAA
.UK
1
Cooling
Heating
7,500
9,200
3.36
3.41
0.09
0.09
0.41
0.41
4.78
4.86
47
47
16
PCA-P5HA
PUH-P5YGAA
.UK
1
Cooling
Heating
13,000
16,000
4.90
4.98
0.26
0.26
1.24
1.24
7.22
7.46
65.5
65.5
PCA-P5HA
PUH-P5YGAA
.UK
1
Cooling
Heating
13,000
16,000
4.90
4.98
0.26
0.26
1.19
1.19
6.85
7.07
65.5
65.5
PCA-P5HA
PUH-P5YGAA
.UK
1
Cooling
Heating
13,000
16,000
4.90
4.98
0.27
0.27
1.14
1.14
6.61
6.82
65.5
65.5