Connecting; Safety Notes - Siemens SITRANS TH400 Operating Instructions Manual

Temperature transmitter
Table of Contents

Advertisement

Connecting

5.1

Safety Notes

Note
National regulations
Be sure to observe the regulations valid and relevant in your country.
Note
To improve the interference immunity:
• Lay signal cables separately from cables with voltages > 60 V.
• Use cables with twisted wires.
• Avoid getting too close to large electrical systems or use shielded cables.
• Use shielded cable to guarantee the full specification according to PROFIBUS PA or
• Use only cable entries and covers that are approved for the relevant use.
• At an ambient temperature T ≥ 60 °C, use heat-resistant cables approved for an ambient
• Use cables with wires that have a maximum cross-sectional area of 2.5 mm
See also
Connection diagrams (Page 24)
Unsuitable cables and/or cable glands
Danger of explosion in hazardous areas.
• Only use suitable cables and cable glands complying with the requirements specified in
• Tighten the cable glands in accordance with the torques specified in Chapter "Technical
• When replacing cable glands use only cable glands of the same type.
• After installation check that the cables are seated firmly.
SITRANS TH400
Operating Instructions, 03/2014, A5E01018688-03
FOUNDATION Fieldbus.
temperature of at least 20 K higher.
WARNING
Chapter "Technical data".
data".
5
.
2
17