Connecting
5.1
Safety Notes
Note
National regulations
Be sure to observe the regulations valid and relevant in your country.
Note
To improve the interference immunity:
• Lay signal cables separately from cables with voltages > 60 V.
• Use cables with twisted wires.
• Avoid getting too close to large electrical systems or use shielded cables.
• Use shielded cable to guarantee the full specification according to PROFIBUS PA or
• Use only cable entries and covers that are approved for the relevant use.
• At an ambient temperature T ≥ 60 °C, use heat-resistant cables approved for an ambient
• Use cables with wires that have a maximum cross-sectional area of 2.5 mm
See also
Connection diagrams (Page 24)
Unsuitable cables and/or cable glands
Danger of explosion in hazardous areas.
• Only use suitable cables and cable glands complying with the requirements specified in
• Tighten the cable glands in accordance with the torques specified in Chapter "Technical
• When replacing cable glands use only cable glands of the same type.
• After installation check that the cables are seated firmly.
SITRANS TH400
Operating Instructions, 03/2014, A5E01018688-03
FOUNDATION Fieldbus.
temperature of at least 20 K higher.
WARNING
Chapter "Technical data".
data".