7.3.2
INSTRUCTION
7 – 6

Air Pressure-Dependent Adjustment

This kind of adjustment can only be carried out by using the diagnostics
tool.
2
A barometer
is required for air pressure-dependent adjustment of the air
flow sensor. The following steps must be taken:
1.
Press the "Settings" button so that you can change the figures in the
diagnosis tool on the "Settings" screen.
MICRO · SENS
®
TITANUS
File
Record
Settings
Status
Sensitivity (Fire alarm)
Alarm delay
Air flow range
Fault delay
Action alarm threshold
Height above sea level
Air pressure
Fan voltage
Reception
2.
Determine the height above sea level (NN) at the aspirating smoke
detection system installation site and enter it in the "Settings" screen.
3.
Using a hand-held barometer, measure the air pressure and enter
this figure in the "Settings" screen in the diagnosis tool as well.
If this measured air pressure does not correspond to the annual average
for that height, then the air flow sensor will not adjust to 0 %.
2
Recommended: Digital precision pocket barometer GPB 1300, Greisinger electronic GmbH
Data: 01/09
TITANUS MICRO·SENS
(Date Time)
Device-Selection
?
Fault messages
Settings
0,500
%/m
s
10
50
%
1
min
40
s
60
%
0
m
1013
hPa
9,0
V
®
ROOM-IDENT
Fault latched
Dynamic air flow
ROOM-IDENT
LOGIC SENS
LOGIC SENS
Fire alarm after
ROOM·IDENT
Set
Active Initialisation
Set
Serial No.