Pipe Design
Branch length
Pipe designs
INSTRUCTION
4 – 4
In order to ensure a short transport time for the smoke fumes in the sam-
pling pipe and thus enable rapid detection, it is better to plan several
shorter than a few long ones (preferably a U- or double U-pipe system ).
4 types of pipe designs can be selected, depending on the cabinet ge-
ometry (see Figure 4.2).
I- pipe
U- pipe
M-pipe
Double U-pipe
The design for fire location should be the I-pipe configuration.
Data: 01/09
TITANUS MICRO·SENS
An air sampling smoke detection pipe system
without branches.
An air sampling smoke detection pipe system
which branches into 2 air sampling branches after
the connection to the TITANUS MICRO ·SENS
An air sampling smoke detection pipe system
which branches into 3 air sampling branches after
the connection to the TITANUS MICRO ·SENS
An air sampling smoke detection pipe system
which branches into 4 air sampling branches after
the connection to the TITANUS MICRO ·SENS
®
®
.
®
.
®
.
MS_A_04-en-e