Product Description

®
2
Product Description
2.1
Features of the TITANUS
air sampling smoke
®
detection system
TOP·SENS
TITANUS
is the latest generation of the renowned WAGNER
®
air sampling smoke detection systems. Besides its use for room and equip-
ment protection the more sensitive system can be used for monitoring cli-
matic cabinets and ducts.
Sensitivity
The device has a display sensitivity of 0.05%/m to 0.0015%/m light obscura-
tion. According to application, further sensitivities can be set. Thanks to the
innovative High-Power-Light-Source technology a wide detection range is
achieved for all types of fire.
The area to be monitored can be doubled if two detector modules are used
TOP·SENS
in TITANUS
. There are three alarm levels for each detector
®
module – alert alarm, action alarm and fire alarm. These can be separately
controlled via voltage-free contacts.
Alternative sensitivity
The set sensitivity of the detector modules can be adjusted one step lower
via an additional input.
·SENS
LOGIC
In order to prevent false alarms, the intelligent signal processing called
·SENS
LOGIC
distinguishes between interferences and the occurrence of
real fire.
Safe airflow monitoring
Like spot-type detectors, which are electronically monitored in order to detect
line fractures and short circuits, air sampling systems require complex and
safe air flow monitoring. The unique air flow sensor technology used in all
WAGNER air sampling smoke detection systems guarantees the detection
of faults such as pipe fractures or blockages of air sampling points.
The low-level air flow is equipped with a dynamic air flow sensor in order to
detect small and quick changes.
Air flow monitoring is temperature compensated and can be adjusted de-
pending on the air pressure.
Networkability
A special feature of TITANUS
is its ability to network the system. With an
®
optional network card in TITANUS
several smoke detection systems can be
®
linked to one network. The operator can oversee the entire system from a
central control point and observe the smoke level, air flow data etc.
Patented detection points
Depending on the required pipe design the air sampling points have defined
hole diameters. For these exact air sampling points WAGNER has devel-