Adjustment Dependent On The Air Pressure - WAGNER TITANUS PRO-SENS Technical Manual

Air sampling smoke detection system
Hide thumbs Also See for TITANUS PRO-SENS:
Table of Contents

Advertisement

Commissioning
160
8.1.2

Adjustment dependent on the air pressure

Figure 96: Adjustment dependent on the air pressure of the air flow sensor of TITA-
NUS PRO·SENS
For the adjustment dependent on the air pressure of the air flow sensor a ba-
rometer (Recommendation: digital precision pocket barometer GPB 1300,
Greisinger electronic) and a multimeter are necessary. Follow the steps be-
low:
1. Make sure the device has been in operation for at least 30 minutes.
2. Determine the height above sea level of the mounting location of the air
sampling smoke detection system and register the value in the commis-
sioning protocol.
3. Measure the air pressure by means of the pocket barometer and the
ambient temperature by means of a temperature measuring instrument.
Register both values in the commissioning protocol.
4. Determine the adjustment value for the air flow sensor according to the
air pressure adjustment charts (refer to appendix) and register the value
in the commissioning protocol. Pay attention that the adjustment chart
corresponds to the design of the pipe system.
®
06/13
PRO·SENS
TITANUS
®