Communication Error Between Indoor Unit And Up-Down Panel; Up-Down Panel Is Defective - koppel KV24 ODU-ARF21C Service Manual

Light commercial air conditioning
Table of Contents

Advertisement

Troubleshooting
2.4.2 For the super-slim cassette with up-down panel

2.4.2.1 Communication error between indoor unit and up-down panel

F7
F0  Displayed
Communication failure between 
indoor unit and up-down panel
Check the wire connection 
between up-down panel and 
No
Correct the connection 
indoor unit, is it right? 
Yes
Replace the up-down panel
No
Replace the indoor main PCB

2.4.2.2 Up-down panel is defective

F8
108
Electrical Control System