Contents Part 1 General Information ....................1 Part 2 Indoor Units ......................... 5 Part 3 Outdoor Units ......................55 Part 4 Installation ......................... 65 Part 5 Electrical Control System ..................91 ※The specifications, designs, and information in this book are subject to change without notice for product improvement.
General Information Part 1 General Information 1. Model Lists .................... 2 2. External Appearance ................3 2.1 Indoor Units ....................... 3 2.2 Outdoor Units ......................3 3. Nomenclature ..................4 General Information...
External Appearance 2. External Appearance 2.1 Indoor Units Concealed Ducted Super slim cassette Ceiling-Floor Floor-standing 2.2 Outdoor Units Single fan outdoor unit Double fan outdoor unit General Information...
Indoor Units Part 2 Indoor Units Super Slim Cassette Type ........... 6 Concealed Ducted Type ............. 19 Ceiling & Floor Type ............34 Floor-standing Type ............44 Indoor Units...
Indoor Units Super Slim Cassette Type 1. Features ................7 2. Dimensions ..............10 3. Service Space ..............11 4. Wiring diagrams .............. 12 5. Electric Characteristics ..........13 6. Sound Levels ..............14 7.
Features 1. Features Overview Compact design, super slim body size, less space requiring in installation Each louver can be separately controlled, more comfort air blowing is possible. Fresh air intake function Fresh air fulfills air quality more healthy and comfortable. ...
Page 10
Features Built-in draining pump Due to improvement of structure, it is now more convenient to repair and replace the drain pump. Drain Pump With built-in pump to make sure condensed water drain out reliably. Terminals for alarm lamp and long-distance on-off controller connection are standard ...
Page 11
Features Alarm lamp Long-distance on-off controller Indoor Units...
Dimensions 2. Dimensions 92 92 Fresh air intake 4-install hanger Body Gas side Liquid side Wiring connection port E-parts box Service hole for Test mouth & Test cover draining pump Drain hole 92 92 92 92 Panel Unit: mm Capacity (KBtu/h) 36/48 Indoor Units...
Electric Characteristics Electric Characteristics Power Indoor Unit Supply Model Voltage KV24CC-ARF21C 220-230 KV36CC-ARF21C 220-230 KV48CC-ARF21C 220-230 KV60CC-ARF21C 220-230 Notes: MFA: Max. Fuse Amps. (A) Indoor Units...
Accessories Accessories Name Shape Quantity Installation paper board Installation Fittings Soundproof / insulation sheath Tubing & Fittings Out-let pipe sheath Out-let pipe clasp Drainpipe Fittings Drain joint Seal ring Remote controller & Its Frame Remote controller & Its Frame(The product you Remote controller holder have might not be provided the following...
The Specification of Power 8. The Specification of Power 60000 Type(Cooling only) 24000 36000 48000 Phase 1- Phase 1- Phase Frequency and 220-230V~, 220-230V~, Voltage 60Hz 60Hz Indoor Unit Power Power Wiring (mm 3×2.5 3×2.5 Circuit Breaker/ 15/10 15/10 Fuse (A) Phase 1- Phase 1- Phase...
Concealed Ducted Type Concealed Ducted Type 1. Features ................20 2. Dimensions ..............23 3. Service Space ..............24 4. Wiring Diagrams ............. 25 5. Static Pressure ..............26 6. Electric Characteristics ..........28 7.
Page 22
Features Features 1.1 Installation accessories: (Optional) Front Board, Canvas Air Passage, Filter, Panel, for easy installation Front Board Filter Panel 1.2 Easy Installation: Two air inlet styles (Bottom side or Rear side) Air inlet from rear is standard for all capacity; air inlet from bottom is optional. ...
Page 23
Features Replace the motor or centrifugal fan Remove the ventilated panel firstly. Remove a half of blower housing and take out the motor with centrifugal fan. Directly remove two bolts, and then replace the motor or centrifugal fan easily. Motor Blower Housing Ventilated Panel...
Page 24
Features 1.7 Built-in display board The standard indoor unit can be controlled by wired controller. There is a display board with a receiver in the E-box. Move out the display, and fix it in other place, even in the distance of 2m. The unit will realized remote control. ...
Page 25
Dimensions Dimensions air inlet from rear side Air filter ( optional ) 4-install hanger Liquid side Gas side 25 Drain pipe 25 Drain pipe Test mouth & Test cover 25 Drain connecting pipe ( for pump ) Fresh air intake Electric control box Air filter ( optional ) air inlet from bottom side...
Page 26
Service Space Service Space Ensure enough space required for installation and maintenance. All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following: Indoor Units...
Page 30
Electric Characteristics Electric Characteristics Power Indoor Unit Supply Model Voltage 220-230 KV24DH-ARF21C 220-230 KV36DH-ARF21C 220-230 KV48DH-ARF21C 220-230 KV60DH-ARF21C Notes: MFA: Max. Fuse Amps. (A) Indoor Units...
Page 32
Accessories 8. Accessories Name Shape Quantity Soundproof / insulation sheath Tubing & Fittings Binding tape Seal sponge Drain joint Drainpipe Fittings (for cooling & heating) Seal ring Wired controller Wired controller & Its Frame , Owner s manual Others Installation manual Magnetic ring (twist the electric wires L EMS &...
Page 33
The Specification of Power The Specification of Power 60000 Type(Cooling only) 24000 36000 48000 Phase 1- Phase 1- Phase Frequency and 220-230V~, 220-230V~, Voltage 60Hz 60Hz Indoor Unit Power Power Wiring (mm 3×2.5 3×2.5 Circuit Breaker/ 15/10 15/10 Fuse (A) Phase 1- Phase 1- Phase...
Page 34
Field Wiring Field Wiring 24K, 36K Indoor Units...
Ceiling & Floor Type Ceiling & Floor Type 1. Features ................35 2. Dimensions ..............36 3. Service Space ..............37 4. Wiring Diagrams ............. 38 5. Electric Characteristics ..........39 6. Sound Levels ..............39 ...
Page 37
Features 1. Features 1.1. New design, modern and elegant appearance. 1.2. Convenient installation --The ceiling type can be easily installed into a corner even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to structure such as one lighting.
Page 38
Dimensions 2. Dimensions Wiring connection port Drain discharge port Fresh air intake Refrigerant pipe hole Hanging arm Capacity (kBtu/h) 1068 1285 1200 48~60 1650 1565 Indoor Units...
Page 39
Service Space 3. Service Space Indoor Units...
Page 41
Electric Characteristics 5. Electric Characteristics Power Indoor Unit Supply Model Voltage 220-230 KV24CM-ARF21C 220-230 KV36CM-ARF21C 220-230 KV48CM-ARF21C 220-230 KV60CM-ARF21C Notes: MFA: Max. Fuse Amps. (A) 6. Sound Levels Microphone 1.5m Air outlet side Microphone Ceiling Floor Noise level dB(A) Model KV24CM-ARF21C KV36CM-ARF21C KV48CM-ARF21C...
Page 42
Accessories 7. Accessories Name Shape Quantity 1. Remote controller Remote controller & Its holder(The product you 2. Remote controller holder have might not be provided the following accessories) 3. Mounting screw (ST2.9×10-C-H) 4. Alkaline dry batteries (AM4) 5. Owner's manual 6.
Page 43
The Specification of Power 8. The Specification of Power 60000 Type(Cooling only) 24000 36000 48000 Phase 1- Phase 1- Phase Frequency and 220-230V~, 220-230V~, Voltage 60Hz 60Hz Indoor Unit Power Power Wiring (mm 3×2.5 3×2.5 Circuit Breaker/ 15/10 15/10 Fuse (A) Phase 1- Phase 1- Phase...
Page 44
Ceiling & Floor Type 9. Field Wiring 24K, 36K Ceiling & Floor Type...
Floor-standing Type Floor-standing Type Features ................45 Dimensions ..............46 Service Space ..............47 Wiring Diagrams ............. 48 Electric Characteristics ..........49 Sound Levels ..............50 Accessories ..............51 ...
Page 47
Features Features 1.1. Fashionable design, modern and elegant appearance. 1.2. Air Outlet Dustproof When turned off, the air outlet louver of the unit can be closed manually to prevent the dust from falling 1.3. Simple and bright panel Adopts simple and bright style panel, suitable for most different space. 1.4.
Page 51
Electric Characteristics 5. Electric Characteristics Power Indoor Unit Supply Model Voltage 220-230 KV36FM-ARF21C 220-230 KV60FM-ARF21C Notes: MFA: Max. Fuse Amps. (A) Floor-standing Type...
Page 54
The Specification of Power 8. The Specification of Power 60000 Type(Cooling only) 36000 Phase 1- Phase Frequency and Voltage 220-230V~, 60Hz Indoor Unit Power Power Wiring (mm 3×2.5 Circuit Breaker/ Fuse (A) 15/10 Phase 1- Phase 3- Phase Frequency and Voltage 220-230V~, 60Hz 220-230V~, 60Hz Outdoor Unit Power...
Page 55
Field Wiring Field Wiring Floor-standing Type...
Outdoor Units Part 3 Outdoor Units Dimensions ..............56 Service Space ..............58 Piping Diagrams .............. 59 Wiring Diagrams ............. 60 Electric Characteristics ..........62 Operation Limits ............. 63 ...
Page 60
Service Space 2. Service Space (Wall or obstacle) Air inlet More than 30cm More than 60cm More than 30cm Maintain channel Air inlet More than 60cm Air outlet More than 200cm Outdoor Units...
Operation Limits 6. Operation Limits Temperature Cooling operation Drying operation Mode Room temperature 17℃~32℃ 17℃~32℃ 0℃~50℃ 0℃~50℃ Outdoor temperature (-15℃~50℃:For the models with low temperature cooling system) CAUTION: 1. If the air conditioner is used beyond the above conditions, certain safety protection features may come into operation and cause the unit to operate abnormally.
Page 66
Sound Levels 7. Sound Levels Outdoor Unit Microphone 1.0m Note: H= 0.5 × height of outdoor unit Model Noise level dB(A) KV24ODU-ARF21C KV36ODU-ARF21C KV48ODU-ARF21C KV60ODU-CRF21C Outdoor Units...
Installation Procedure 1. Installation Procedure Indoor unit installation Outdoor unit installation location selection location selection Indoor unit installation Outdoor unit installation Refrigerant pipe Refrigerant pipe installation and insulation installation and insulation Drainage pipe installation Drainage pipe installation and insulation and insulation Vacuum drying and leakage checking Additional refrigerant charge Insulating the joint part of refrigerant pipe...
Location selection 2. Location selection 2.1 Indoor unit location selection The place shall easily support the indoor unit’s weight. The place can ensure the indoor unit installation and inspection. The place can ensure the indoor unit horizontally installed. ...
Indoor unit installation 3. Indoor unit installation 3.1 Super slim cassette indoor unit installation 3.1.1 Service space for indoor unit Capacity(KBtu) >235 36/48 >275 >317 3.1.2 Bolt pitch 3.1.3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling.
Page 71
Indoor unit installation 3.1.4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure the levelness of the main body is within ±1°.
Page 72
Indoor unit installation Remove the 4 corner covers. Hang the panel to the hooks on the mainbody. If the panel is with auto-lift grille, please watch the ropes lifting the grille, DO NOT make the ropes enwinded or blocked. Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate water.
Page 73
Indoor unit installation Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively. Install the 4 corner covers back. Note: The panel shall be installed after the wiring is connected. Installation...
Page 74
Indoor unit installation 3.2 Concealed duct indoor unit installation 3.2.1 Service space for indoor unit 3.2.2 Bolt pitch Size of outline dimension mounted plug Capacity(KBtu) 1240 48/60 1240 3.2.3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling.
Page 75
Indoor unit installation 3.2.4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure the levelness of the main body is within ±1°.
Page 76
Indoor unit installation 3.2.7 Change the air inlet direction ① Take off ventilation panel and flange, cut off the staples at side rail. ② Stick the attached seal sponge as per the indicating place in the following fig, and then change the mounting positions of air return panel and air return flange .
Page 77
Indoor unit installation 3.3 Ceiling & floor indoor unit installation 3.3.1 Service space for indoor unit 3.3.2 Bolt pitch ① Ceiling installation Capacity (KBtu/h) 1200 48~60 1565 ② Wall-mounted installation 3.3.3 Install the pendant bolt ① Ceiling installation Installation...
Page 78
Indoor unit installation Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings). ② Wall-mounted installation Install the tapping screws onto the wall.(Refer to picture below) 3.3.4 Install the main body ①...
Page 79
Indoor unit installation Put the side panels and grilles back. ② Wall-mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of body can touch with floor or suspended, but the body must install vertically.) Installation...
Page 80
Indoor unit installation 3.4 Floor standing indoor unit installation 3.4.1 Service space for indoor unit a. A place which provides the spaces around the indoor unit as required above in the diagram. b. A place where is no obstacle near the inlet and outlet area. c.
Page 81
Outdoor unit installation (Side Discharge Unit) 3.4.2.3. Take the Pipe Clip off before connecting the pipes and wiring; fit it when these finished. Use accessories to connect the pipes/wires on both sides and back side. 4. Outdoor unit installation (Side Discharge Unit) 4.1 Service space for outdoor unit (Wall or obstacle) More than 30cm...
Refrigerant pipe installation 4.2 Bolt pitch For the value of A and B, please refer to the dimension part. 4.3 Install the Unit Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. Never hold the inlet of the outdoor unit to prevent it from deforming.
Page 83
Refrigerant pipe installation Lean Crude Burr 5.2.5 Insulate the copper pipe Before test operation, the joint parts should not be heat insulated. 5.2.6 Flare the pipe Insert a flare nut into the pipe before flaring the pipe According to the following table to flare the pipe Flare dimension A (mm) Pipe diameter...
6. Drainage pipe installation Drainage pipe installation Install the drainage pipe as shown below and take measures against condensation. Improperly installation could lead to leakage and eventually wet furniture and belongings. 6.1 Installation principle Ensure at least 1/100 slope of the drainage pipe ...
Page 85
6. Drainage pipe installation 6.2.3 Individual design of drainage pipe system The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe and drainage pipe in building. The drainage pipe of the indoor unit with water pump should be apart from the one without water pump. 6.2.4 Supporter gap of drainage pipe ...
Page 86
6. Drainage pipe installation Indoor unit More than 50mm Plug More than 25mm Water storage pipe 6.2.7 Lifting pipe setting of indoor unit with water pump The length of lifting pipe should not exceed the pump head of indoor unit water pump. Pump head of big four way cassette: 750mm Pump head of compact four way cassette: 500mm ...
Page 87
6. Drainage pipe installation 6.3 Drainage test 6.3.1 Water leakage test After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to check whether there is leakage at joint section. 6.3.2 Water discharge test Natural drainage mode(the indoor unit with outdoor drainage pump) Infuse above 600ml water through water test hole slowly into the water collector, observe whether the water can discharge through the transparent hard pipe at drainage outlet.
7. Vacuum Drying and Leakage Checking Vacuum Drying and Leakage Checking 7.1 Purpose of vacuum drying Eliminating moisture in system to prevent the phenomena of ice-blockage and copper oxidation. Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor. ...
8. Additional refrigerant charge Additional refrigerant charge After the vacuum drying process is carried out, the additional refrigerant charge process need to be performed. The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided by the diameter and length of the liquid pipe between indoor and outdoor unit.
10. Engineering of electrical wiring 9.2.3 Insulation material selection for drainage pipe The insulation material should be flame retardant material, the flame retardancy of the material should be selected according to the local law. Thickness of insulation layer is usually above 10mm. ...
11. Test operation Test operation 11.1 The test operation must be carried out after the entire installation has been completed. 11.2 Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed.
Electrical Control System Part 5 Electrical Control System Electrical Control Function ........92 Troubleshooting ............100 Controller ..............125 Electrical Control System...
Page 94
Control Function Electrical 1. Electrical Control Function 1.1 Definition T1: Indoor room temperature T2: Coil temperature of indoor heat exchanger middle. T2B: Coil temperature of indoor heat exchanger outlet. T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 1.2 Main Protection 1.2.1 Time delay at restart for compressor.
Electrical Control Function 1.3 Operation Modes and Functions 1.3.1 Fan mode (1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) The louver operates same as in cooling mode. (4) Auto fan: High Medium 1.3.2 Cooling Mode...
Page 96
Control Function Electrical 1.3.2.3 Evaporator low temperature T2 protection. >= ---T2<0℃, the compressor will stop and restart when T2 5℃. ---0℃≦T2<4℃, the compressor frequency will be limited and decreased to the lower level ---4℃≤T2<7℃, the compressor will keep the current frequency. ---T2>7℃, the compressor frequency will not be limited.
Page 97
Electrical Control Function 1.3.5 Timer function 1.3.5.1 Timing range is 24 hours. 1.3.5.2 Timer on. The machine will turn on automatically when reaching the setting time. 1.3.5.3 Timer off. The machine will turn off automatically when reaching the setting time. 1.3.5.4 Timer on/off.
Page 98
Control Function Electrical 1.3.9 Follow me(Optional) If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not respond.
Page 99
Electrical Control Function The frequency after the frequency limit The frequency of sending to 341 Indoor unit evaporator outlet temp.(heating T2, If the temp. is lower than -9 degree, the digital display tube will cooling T2B) show “-9”.If the temp. is higher than 70 degree, the digital Condenser pipe temp.(T3) display tube will show “70”.
Page 100
Control Function Electrical If the temp. is lower than -9 degree, the digital display tube will show “9”.If the temp. is higher than 70 degree, the digital Indoor room temp. of 1# indoor unit display tube will show “70”. If the capacity demand is 0, , the digital display tube will show “0.
Page 101
Electrical Control Function Shutdown stop Electrical disconnect DR stop Electrical Control System...
Troubleshooting 2. Troubleshooting 2.1 Display board 2.1.1 Icon explanation on indoor display board (Super slim cassette). 2.1.2 Icon explanation on indoor display board (Duct) PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type) Alarm indicator Timer indicator Infrared signal receiver Operation lamp Display digital tube Temporary button...
Page 103
Troubleshooting 2.1.5 Display board of floor-standing Electrical Control System...
Page 104
Troubleshooting 2.2 Indoor unit malfunction For floor standing Malfunction Error Code Indoor EEPROM malfunction Communication malfunction between indoor and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Refrigerant leakage detection Outdoor unit is faulty (for old communication protocol) Overcurrent protection (For some units) Open or short circuit of T4 temperature sensor...
Page 105
Troubleshooting For other type: Operation Lamp Malfunction Error Code Timer Lamp (flashes) Indoor EEPROM malfunction Communication malfunction between indoor and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Refrigerant leakage detection Water level alarm Communication error between master and slave unit (for twins system) Another indoor unit malfunction (for twins system)
Page 106
Troubleshooting 2.3 Outdoor unit malfunction Display Malfunction or Protection Communication malfunction between indoor and outdoor units Overcurrent protection Ambient temperature sensor (T4) is malfunction Outdoor heat-exchanger temperature sensor (T3) is malfunction Discharge temperature sensor (T5) is malfunction Outdoor EEPROM is malfunction IPM module protection Voltage protection (too high or too low) Protection of ultra-low ambient temperature...
Page 107
Troubleshooting 2.4 Solving steps for typical malfunction 2.4.1 For the indoor unit 2.4.1.1 Open or short circuit of temperature sensor 2.4.1.2. Outdoor unit malfunction Electrical Control System...
Page 108
Troubleshooting 2.4.1.3. Indoor EEPROM malfunction EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. 2.4.1.4. Water-level alarm malfunction Electrical Control System...
Page 109
Troubleshooting 2.4.1.5. Refrigerant Leakage Detection 2.4.1.6 Communication malfunction between indoor and outdoor units The same as E1 in outdoor. Electrical Control System...
Page 110
Troubleshooting 2.4.2 For the super-slim cassette with up-down panel 2.4.2.1 Communication error between indoor unit and up-down panel F0 Displayed Communication failure between indoor unit and up-down panel Check the wire connection between up-down panel and Correct the connection indoor unit, is it right? Replace the up-down panel Replace the indoor main PCB 2.4.2.2 Up-down panel is defective Electrical Control System...
Page 111
Troubleshooting 2.4.3 For the unit with TWINS function (For the super-slim cassette & A5 duct) 2.4.3.1 Communication between master unit and indoor unit malfunction 2.4.3.2 Other malfunction between master unit and indoor unit One indoor unit displays ”E9”, which means another indoor unit is faulty. Check another indoor unit’s error code and then follow the appropriate solutions to solve the malfunction.
Page 112
Troubleshooting 2.4.4 For the outdoor unit 2.4.4.1. F4 malfunction EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. Electrical Control System...
Page 113
Troubleshooting 2.4.4.2. E1 malfunction For 485 communication Electrical Control System...
Page 114
Troubleshooting 2.4.4.3. J4 malfunction Electrical Control System...
Page 115
Troubleshooting 2.4.4.4. F1, F2, F3 malfunction Error E4 display Judge 1: Outdoor condenser temp. sensor (T3) is malfunction Check whether the wiring of the condenser temp. sensor(T3) is Connect the wiring well broken off Check whether the resistance of condenser temp. sensorT3) is wrong Replace condenser temp. sensor(T3) refer to the Appendix 1 Judge 2: Outdoor ambient temp. sensor (T4) is malfunction Check whether the wiring of the outdoor ambient temperature Connect the wiring well sensor (T4) is broken off Check whether the resistance of outdoor ambient temperature Replace outdoor ambient sensor (T4) is wrong refer to the temperature sensor (T4) Appendix 1 Judge 3: Compressor discharge temp. sensor (T5) is malfunction Check whether the wiring of the compressor discharge temperature Connect the wiring well sensor (T5) is broken off Check whether the resistance of ...
Page 116
Troubleshooting 2.4.4.5. P6 malfunction Electrical Control System...
Page 117
Troubleshooting 2.4.4.6. J5 malfunction Electrical Control System...
Page 118
Troubleshooting 2.4.4.7. J6 malfunction P2 display Low pressure protection Whether the wiring between the low pressure protector and main control Connect it well board is connected well or correctly Whether the low pressure protector is broken Method: Disconnect the plug. Measure the resistance of the low pressure protector.
Page 119
Troubleshooting 2.4.4.8. F0 malfunction Electrical Control System...
Page 120
Troubleshooting 2.4.4.9. J2 malfunction When compressor discharge temperature is higher than 115°C, the unit will stop, and unit runs again when compressor discharge temperature is lower than 90°C. P4 display Temperature protection of compressor discharge Check whether the Check whether the compressor discharge temp. is Stop leaking and add refrigerant refrigerant is leak more than 115°C ? Check whether connection is right between compressor discharge temp.
Page 121
Troubleshooting 2.4.4.10. J1 malfunction When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. P5 display Check the connection between temperature Correct the connection High temperature protection of sensor and PCB. condenser Check whether the condenser temperature is Check whether the Higher than 65°C resistance of condenser...
Page 122
Troubleshooting 2.4.4.11. P0 malfunction At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is defective. Otherwise, please follow the procedure below: Electrical Control System...
Page 123
Troubleshooting 2.4.4.12. J0 malfunction Electrical Control System...
Page 124
Troubleshooting Appendix 1 Temperature Sensor Resistance Value Table (℃--K) ℃ ℃ ℃ ℃ K Ohm K Ohm K Ohm K Ohm 12.6431 2.35774 0.62973 115.266 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241 0.57683 89.5865 10.4736 2.03732 0.56038 84.2190 10.000...
Page 126
Troubleshooting Appendix 3 Normal voltage of P and N 208-240V(1-phase,3-phase) 380-420V(3-phase) In standby 310VDC around 530VDC around In operation With passive PFC With partial active With fully active module PFC module PFC module >200VDC >310VDC >370VDC >450VDC Electrical Control System...
Page 127
Controller 3. Controller 3.1Wireless Remote Controller 3.1.1RG51Q1/BGE General Function for wireless remote controller: Model RG51Q1/BGE Rated voltage 3.0V(2pieces of LR03 7# batteries) Min voltage for sending signal of CPU 2.4V Effective receiving distance 8m~11m Operation condition -5~60℃ Electrical Control System...
Page 128
Controller Buttons and functions : Decrease the set temp. Keeping pressing will decrease the temp with 1℃ per 0.5s. 1. Adjust : Increase the set temp. Keeping pressing will increase the temp with 1℃ per 0.5s. 2. Adjust 3. MODE: Once pressing, running mode will be selected in the following sequence: AUTO COOL HEAT...
Page 129
Controller 3.1.2 RG51C/E Remote Controller Specifications Model RG51C/E Rated Voltage 3.0V(2pieces of LR03 7# batteries) Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it can get 11m) Environment Temperature Range -5℃~60℃ Introduction of Function Buttons on the Remote Controller SET TEM PERATURE( C) AU TO COOL...
Page 130
Controller controls into faceplate setting state and the LCD shows F2.Press the TEMPUP( ) to control the faceplate up and press the TEMP DOWN( ) to control the faceplate down. Press any button to exit the faceplate setting state, then the LCD back to the normal display. 7.
Page 131
Controller 3.1.3 R51M/(C)E Remote Controller Specifications Model R51M/(C)E Rated Voltage 3.0V Reaching Distance Environment Temperature Range -5℃~60℃ Introduction of Function Buttons on the Remote Controller : Decrease the set temp. Keeping pressing will decrease the temp with 1℃ per 0.5s. 1.
Page 132
Controller AUTO HIGH 9. ON/OFF: For turning on or turning off the air conditioner 10. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting.
Page 133
Controller 3.2 Wired Remote Controller 3.2.1 KJR-12B Name and functions of buttons on the wire controller Mode button: When press this button, the operation mode change as the following sequence: AUTO COOL HEAT Remark: For the cooling only model, the heating mode is skipped. Timer on button: Press this button, timer on function is active.
Page 134
Controller Adjust button: Set indoor temperature up. If press and hold on, it will increase at 1degree per 0.5 second. Adjust button: Set indoor temperature down. if press and hold on, it will decrease at 1degree per 0.5 Second. 10. Swing button: First press, start swing function; second press, stop swing. (Match to some model with swing function).
Page 135
Controller The wired controller will reset to factory setting with auto mode, auto fan and 24℃ setting temperature when the air conditioner restarts after power failure. And this may cause inconsistent displays on the wired controller and on the air conditioner. You need to readjust the running status through the wired controller.