Page 1
+/- 1 DEG ANGULAR INFORMATION BELONGING DR20I4-AAS*J TO WINCO, DR20I4 UNAUTHORIZED USE IS MODEL: PROHIBITED 1 of 1 M10817 PART: ALL DIMESNIONS INCH WINCO INC. 225 S. CORDOVA AVE. LE CENTER, MN 56057 SERVICE DEPT. 507-357-6831 • SALES DEPT. 507-357-6821 www.wincogen.com...
TABLE OF CONTENTS COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours. If you should ever need to contact us on this unit, it will help us to SAVE THESE INSTRUCTIONS respond to your needs faster.
SAFETY INFORMATION A. Operate only in well ventilated areas. B. Never operate indoors including attached garages This engine generator set has been designed and manufactured to C. Never operate the unit in such a way as to allow exhaust gases allow safe, reliable performance.
Engine Fluid Specifications GENERATOR SET Fuel ASTM D-975 -1D or 2D Every WINCO generator set has its own unique identity data plate. EN590 or equivalent This data plate identifies the complete unit model number, the system Oil Type SEE LUBRICATION SECTION serial number, and has links to the individual components that form the Oil Capacity 8.8 Quarts...
These WINCO units let WINCO take care of the freight claim. If you sign for the unit, the are equipped with generators manufactured by Cummins Generator transfer of the ownership requires that you file the freight claim Technology.
fuel can cause a shift in the balance of the fuel tank, making for a loose. These units must be mounted to a steel or concrete base. DANGEROUS, unbalanced lifting load. If the generator was shipped on The unit should be mounted to allow ample working room around it. the fuel tank, use the lifting points located on the fuel tank to move the entire generator set into place.
COOLANT WARNING: The electrolyte is diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following WARNING: PERSONAL INJURY: precautions must always be taken. Never open a hot radiator cap. 1. Always wear full eye protection and protective clothing. 2.
WARNING: The block heater on this unit is a 750 watt heater can use the same 20 Amp GFCI fused circuit. This circuit will terminate on the 120 Make sure the generator is disconnected from the battery to prevent Volt terminal block mount in the customer connection cabinet. The accidental starting.
F: NEUTRAL TO GROUND LEAD LUG: labeled START is your remote start lead. Closing these two leads This lug is provided on the neutral terminal block to allow you to run together will signal the DSE7310 to go into an autostart mode and start a neutral to ground lead if you are using the generator in a stand up the generator.
ASCO 300 UL SWITCH PROTECTIONS ASCO 300 UL SWITCH top terminals. installed. If your When an alarm is present, the common alarm LED if configures will Emergency illuminate. The LCD display will show an icon to indicate the failure. witch to these hout either the alled.. WARNINGS Warnings are non-critical alarm conditions and do not affect the failure relay input operation of the generator system, they serve to draw the operator’s ller.
Note: Wire #93 is energized to turn on the glow plugs for 15 seconds warning light. Simply reset the ATS start over. first and then the starter and fuel solenoid are engaged. Once you have completed testing of the ATS, be sure you ALWAYS If the engine fails to start during this cranking period, the starter motor leave the system in the standby mode,unless servicing the unit.
TROUBLESHOOTING TABLE VOLTAGE REGULATOR WIRING Problem Possible Causes AS480 Automatic Voltage Regulator Unit will not crank when power fails Digital genset not in AUTO Transfer control switch not in The following is a list of connections on the AVR. These have been AUTOMATIC position Incorrect wiring between ATS and genset factory set and other than voltage adjustment, should never be Defective control relay in ATS...
WIRING SIZE TABLE The table below is based on Table 310.15 (B) (16) un the National Electric Code 2014 edition. Allowable ampacitier of insulated conductrs rated 0 through 2000V, 75°C through 90°C. Not more than three current-carrying conductors in Raceway, Cable, or Earth (direct buried). Adjust for 40°C (104°F) ambient temperature. Copper Copper Aluminum Aluminum 75°C 90°C Copper Clad Alluminim Copper Clad Aluminum 75°C 90° Wire Type: Wire Type: SIZE AWG Wire Type: Wire Type: RHW, THHW, THW, THWN, TBS, SA, SIS, FEP, FEPB, MI, RHH, OR KCMIL RHW, THHW, THW, TBS, SA, SIS, THHN,...
THREE PHASE AC WIRING HIGH AND LOW WYE HIGH AND LOW WYE THREE PHASE AC WIRE HIGH AND LOW WYE THREE PHASE-HIGH WYE THREE PHASE-LOW WYE THREE PHASE-HIGH WYE THREE PHASE-LOW WYE 277/480 VOLTS 120/208 VOLTS 277/480 VOLTS 120/208 VOLTS THREE PHASE - HIGH WYE 277/480V THREE PHASE - LOW WYE 120/208V SINGLE PHASE AC...
WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO’s option, material found to be defective in material or workmanship under normal use and service will be repaired or replaced.