Setting Up Pro-Dialog Plus Control; User Interface General Features - Carrier 30RQ Operation And Maintenance Instructions

Pro-dialog plus control
Table of Contents

Advertisement

4 - SETTING UP PRO-DIALOG PLUS CONTROL

4.1 - User interface general features

Dual-circuit chiller interface
Main interface
Menu block
Triple-circuit chiller interface
Main interface
Menu block
Main interface
Button
Name
Description
Menu
Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.
Up arrow
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises increase of the
value of any parameter.
Down arrow
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises decrease of the
value of any parameter.
Enter
Gives access to the modification mode, validates a modification or displays expanded item description.
Start/stop
Authorises start or stop of the chiller in local mode or modification of its operating type.
Main interface menu LEDs
LED
Name
INFORMATION menu
TEMPERATURES menu
PRESSURES menu
SETPOINTS menu
INPUTS menu
OUTPUTS/TESTS menu
CONFIGURATIONS menu Displays the unit configuration and enables it to be modified.
ALARMS menu
ALARMS HISTORY menu Displays the history of the alarms.
OPERATING LOG menu
Summary interface
A
A
B
B
A A
B B
Summary interface
A
A
B
B
C
C
A
A
B
B
C
C
Description
Displays the general operating parameters for the unit.
Displays the unit operating temperatures.
Displays the unit operating pressures.
Displays the unit setpoints and enables them to be modified.
Displays the status of the unit digital and analogue inputs.
Displays the status of the unit outputs and enables them to be tested.
Displays active alarms.
Displays the operating times and number of starts for the unit and the compressors.
Dual-circuit heat pump interface
Main interface
R
Menu block
The local interface enables a number of operating para-
meters to be displayed and modified. The interface consists
of two distinct parts: the main interface (left hand section)
and the summary interface (right hand section).
R
Main interface
It gives access to all Pro-Dialog Plus data and operating
functions. It consists of:
A two-digit display showing the number of the item
selected.
A four-digit display showing the contents of the item
selected.
LEDs and buttons for unit start/stop, menu selection,
menu item selection and value adjustment.
Summary interface
A A
B B
A A
B B
7