Carrier 30RQ Operation And Maintenance Instructions page 20

Pro-dialog plus control
Table of Contents

Advertisement

Submenu outputs 2 (selection) (continued)
Item
Format
Units
8
On
OFF
tESt
9
b
b
b
1
2
3
10
b
b
b
1
2
3
tESt
11
nn.n
tESt
12
b
b
1
2
13
YES/no
4.3.10.3 - Manual tests
This function allows the user to test the outputs individually,
if the machine is completely shut down (LOFF). To carry
out a manual test use the arrow keys to access the output to
be tested and press the Enter key (longer than 2 seconds)
to activate the modification mode. The password is auto-
matically requested, if it has not previously been verified.
The Outputs/Test LED on the user interface begins to flash.
Enter the desired test value and again press Enter to start
the test. 'TESt' is displayed on the 4-digit display alternately
with the value tested. The Outputs/Test LED stops flashing.
Press the Enter key or an arrow key to stop the test.
4.3.11 - Description of the Configuration menu
4.3.11.1 - General
This menu can be used to display and modify all configura-
tions: Factory, Service and User. Only the User Configuration
can be modified by the end-user. The Factory, Service and
master/slave configurations are not described in this
document. A configuration can only be modified if the unit
is fully stopped (LOFF).
The menus User 1 [USEr 1] and User 2 [USEr 2] are
password-protected. The other menus are directly accessible,
except if item 11 of the User 2 menu (password for all
configurations) has been validated.
20
Description
Boiler operating status.
On: operating
OFF: stopped
Free cooling 3-way valve status (only displayed when the free cooling option is selected).
b
= 3-way valves, circuit A
1
b
= 3-way valves, circuit B
2
b
= 3-way valves, circuit C
3
0 corresponds to a closed valve (cooling position) and 1 corresponds to an open valve (free cooling position)
Free cooling refrigerant pump status (only displayed when the free cooling option is selected).
b
= pump, circuit A
1
b
= pump, circuit B
2
b
= pump, circuit C
3
Unit capacity 0-10 V signal value (10 V = 100 %). Only displayed if the energy management option is selected.
Chiller operating status
b
= ready (ready-to-start or in operation)
1
b
= in operation
2
Used for local interface test only. Lights or flashes all LEDs and blocks, so as to check that they are working properly.
4.3.11.2 - Password
A password must be entered in order to access the test
function or to modify a configuration. It is automatically
requested, if necessary: 'EntEr PASS' is displayed on the
4-digit display and the configuration menu LED flashes,
indicating that the modification mode is active. Press the
arrow keys until the value '11' is displayed on the 4-digit
display. Press Enter to validate this. The configuration menu
LED stops flashing. If the password is correct, 'Good' is
displayed. If the password is incorrect, 'PASS incorrEct' is
displayed. The User password has a default value of 11.
This value can be modified through the Service configuration.
The password can be entered if the unit is fully stopped,
otherwise 'ACCES dEniEd' (access denied) will be displayed
on the 4-digit display. The controller automatically deacti-
vates the password after 5 minutes without activity (i.e. no
buttons pressed) or after powering up.