Toshiba MMD- AP0724H2UL Service Manual page 61

Multi type
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
controller
Check code
F29
F31
F31
01: Compressor 1
side
02: Compressor 2
side
H01
H01
03: Compressor 3
side
01: Compressor 1
side
02: Compressor 2
side
03: Compressor 3
side
H02
H02
01: Compressor 1
side
02: Compressor 2
H03
H03
side
03: Compressor 3
side
H05
H05
H06
H06
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Location
of
Description
detection
Sub-code
Indoor
Other indoor
unit
error
I/F
Outdoor
EEPROM
error
IPDU
Compressor
breakdown
IPDU
Compressor
error (lockup)
MG-CTT error
IPDU
Current
detection
circuit error
I/F
TD1 sensor
miswiring
(incomplete
insertion)
I/F
Activation of
low-pressure
protection
System
Error detection
status
condition(s)
Stop of
Indoor P.C. board does not
corresponding
operate normally.
unit
All stop *1
Outdoor P.C. board (I/F)
does not operate normally.
All stop
Inverter current detection
circuit detects overcurrent
and shuts system down.
All stop
Overcurrent is detected
several seconds after
startup of inverter
compressor.
All stop
Current flow of at least
specified magnitude is
detected despite inverter
compressor having been
shut turned off.
All stop
Discharge temperature of
compressor 1 (TD1) does
not increase despite
compressor being in
operation.
All stop
Low-pressure Ps sensor
detects operating pressure
lower than 0.02MPa.
– 61 –
Check items (locations)
• Check for defect in indoor P.C.
board (faulty EEPROM)
• Check power supply voltage.
• Check power supply noise.
• Check for defect in outdoor
P.C. board (I/F).
• Check power supply voltage.
(AC208/220V± 10%)
• Check for defect in
compressor.
• Check for possible cause of
abnormal overloading.
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check for defect in
compressor.
• Check power supply voltage.
(AC208/220V± 10%)
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on A3-
IPDU P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
entrapment inside
compressor.)
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check outdoor MG-CTT.
• Check current detection circuit
wiring.
• Check defect in outdoor P.C.
board (A3-IPDU).
• Check installation of TD1
sensor.
• Check connection of TD1
sensor connector and wiring.
• Check resistance
characteristics of TD1 sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check service valves to
confirm full opening
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2).
• Check for defect in SV2 or SV4
circuits.
• Check for defect in low-
pressure Ps sensor.
• Check indoor filter for clogging.
• Check valve opening status of
indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor fan
(during heating).
• Check for insufficiency in
refrigerant quantity.
MG-CTT: Magnet contactor

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd- ap0964h2ul

Table of Contents