Control Outline - Toshiba MMD- AP0724H2UL Service Manual

Multi type
Table of Contents

Advertisement

No.
Item
1
When power
supply is reset
2
Operation
mode selection
3
Room temp.
control

7. CONTROL OUTLINE

Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are
distinguished and the control is selected according to the
distinguished result.
2) Setting of indoor fan speed and existence of air direction
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
3) If resetting the power supply during occurrence of a trouble,
the check code is once cleared. After ON/OFF button of the
remote controller was pushed and the operation was re-
sumed, if the abnormal status continues, the check code is
again displayed on the remote controller.
1) Based on the operation mode selecting command from the
remote controller, the operation mode is selected.
Remote controller
command
STOP
FAN
DRY
COOL
HEAT
1) Adjustment range: Remote controller setup temperature (°F [°C] )
Wired type
64°F [18°C] to 84°F [29°C]
Wireless type
64°F [18°C] to 86°F [30°C]
2) Using the Item code 06, the setup temperature in heating
operation can be corrected.
Setup data
Setup temp.
Correction
[+0°C]
Setting at shipment
Setup data
Control outline
Air conditioner stops.
Fan operation
Drying operation
Cooling operation
Heating operation
COOL/DRY
0
2
4
+0°F
+3.6°F
+7.2°F
[+2°C]
[+4°C]
2
– 16 –
Remarks
Air speed (rpm)/
Air direction adjustment
HEAT
64°F [18°C] to 84°C [29°C]
61°F [16°C] to 86°F [30°C]
Shift of suction
temperature in heating
operation
6
+10.8°F
Except while sensor of
[+6°C]
the remote controller is
controlled
(Code No. [32], "0001")

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd- ap0964h2ul

Table of Contents