Performance Data - Goodman GSX160181F Series Technical Manual

Table of Contents

Advertisement

PERFORMANCE DATA

Model: GSX160181F*/CA*F3636*6D+TXV+EEP
Conditions: 80F/60F IWB @ 650 CFM
Outdoor Temp
Total Btuh
75°
18, 900
80°
18, 700
85°
18, 500
90°
18, 250
95°
18, 000
100°
17, 550
105°
17, 100
110°
16, 450
115°
15, 800
Mode l: GSX160301F*/CA*F3743*6D+TXV+EEP
Conditions: 80F/60F IW B @ 1000 CFM
Outdoor Temp
Total Btuh
75°
30,500
80°
30,100
85°
29,700
90°
29,350
95°
29,000
100°
28,300
105°
27,600
110°
26,550
115°
25,500
Sensible
Latent
Total Watts
Btuh
Btuh
13,986
4,914
1,360
13,838
4,862
1,395
13,690
4,810
1,430
13,505
4,745
1,465
13,320
4,680
1,500
12,987
4,563
1,530
12,654
4,446
1,560
12,173
4,277
1,580
11,692
4,108
1,600
Sensible
Latent
Total
Btuh
Btuh
W atts
23,180
7,320
2,180
22,876
7,224
2,240
22,572
7,128
2,300
22,306
7,044
2,360
22,040
6,960
2,420
21,508
6,792
2,465
20,976
6,624
2,510
20,178
6,372
2,550
19,380
6,120
2,600
GSX160[18-36]1F*
Model: GSX160241F*/CA*F3636*6D+TXV+EEP
Conditions: 80F/60F IWB @ 750 CFM
Outdoor Temp
Total Btuh
75°
24, 800
80°
24, 500
85°
24, 200
90°
23, 900
95°
23, 600
100°
23, 000
105°
22, 400
110°
21, 600
115°
20, 800
Model: GSX160361F*/CA*F4860*6D+TXV+EEP
Conditions: 80F/60F IWB @ 1200 CFM
Outdoor Temp
Total Btuh
75°
36, 500
80°
36, 100
85°
35, 700
90°
35, 250
95°
34, 800
100°
33, 950
105°
33, 100
110°
32, 900
115°
32, 700
Sensible
Latent
Total Watts
Btuh
Btuh
18,600
6,200
1,770
18,375
6,125
1,825
18,150
6,050
1,880
17,925
5,975
1,925
17,700
5,900
1,970
17,250
5,750
2,005
16,800
5,600
2,040
16,200
5,400
2,110
15,600
5,200
2,180
Sensible
Latent
Total Watts
Btuh
Btuh
28,105
8,395
2,610
27,797
8,303
2,685
27,489
8,211
2,760
27,143
8,108
2,830
26,796
8,004
2,900
26,142
7,809
2,960
25,487
7,613
3,020
25,333
7,567
3,070
25,179
7,521
3,120
23