3-2. Electrical parts specification
Model
Parts
name
Tranrsformer
Room
temperature
thermistor
Liquid pipe
thermistor
Gas pipe
thermistor
Fuse
(Indoor con-
troller board)
Fan motor
(with Inner-
thermostat)
Inner-
thermostat/
thermofuse
(Fan motor)
Fan motor
capacitor
Linear
expansion valve
Power supply
terminal bed
Transmission
terminal bed
7
PFFY-P20
PFFY-P25
Symbol
VLEM-A
VLEM-A
VLRM-A
VLRM-A
T
(Primary) 50/60Hz 220-240V
TH21
Resistance 0°C/15kΩ,10°C/9.6kΩ,20°C/6.3kΩ,25°C/5.4kΩ,30°C/4.3kΩ,40°C/3.0kΩ
TH22
Resistance 0°C/15kΩ,10°C/9.6kΩ,20°C/6.3kΩ,25°C/5.4kΩ,30°C/4.3kΩ,40°C/3.0kΩ
TH23
Resistance 0°C/15kΩ,10°C/9.6kΩ,20°C/6.3kΩ,25°C/5.4kΩ,30°C/4.3kΩ,40°C/3.0kΩ
FUSE
4-pole
MF1,2
OUTPUT 15W
OUTPUT 15W
CU-0206B-A
CU-0206B-A
C1
LEV
TB2
TB5
TB15
PFFY-P32
VLEM-A
VLRM-A
250V 6.3A
4-pole
4-pole
OUTPUT 18W
CU-0207B-A
OFF 130°C±5°C
ON 90°C±20°C
1.5µF X 440V
DC12V Stepping motor drive port
dimension 3.2Ω (0~2000pulse)
EDM-402MD
(L,N,
) 330V 30A
(1,2),(M1,M2,S) 300V 10A
PFFY-P40
PFFY-P50
VLEM-A
VLEM-A
VLRM-A
VLRM-A
(Secondary) (18.4V 1.7A)
4-pole
4-pole
OUTPUT 30W
OUTPUT 35W
CU-0303B-A
CRC4415AB
2.0µF
X
440V
PFFY-P63
VLEM-A
VLRM-A
4-pole
OUTPUT 50W
CU-0507B-A
FUSE
+5
152°C
°C
0
CUT OFF
2.5µF
X
440V

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents