Program Used For Setting - Mitsubishi Electric MELSEC FX Series User Manual

Programmable logic controllers
Hide thumbs Also See for MELSEC FX Series:
Table of Contents

Advertisement

FX communication
4.2.6

Program Used for Setting

M8038
0
Make sure to write the program above step 0 as the N:N network parameter setting program.
This program does not require to be executed, because it becomes effective automatically when it
is programmed in this position.
Note:
• Setting of the parameters for the N:N network is started at step 0 (LD M8038), and
finished when any instruction or device other than the program above is processed.
FNC 12
K 0
D8176
MOV
FNC 12
K 2
D8177
MOV
FNC 12
K 1
D8178
MOV
FNC 12
K 3
D8179
MOV
FNC 12
K 6
D8180
MOV
Station No. setting:
Required for master
station (Set range: 0 to 7)
Total number of slave
stations: 2
(Setting range: 1 to 7)
Refresh range setting:
Pattern 1
(Set range: 1 to 2)
Retry count setting:
3 (3times)
Comms time-out setting:
6 (60ms)
N:N network 4
Not required for
slave station
4-6