Pentair FLECK 5600SXT Service Manual page 21

Hide thumbs Also See for FLECK 5600SXT:
Table of Contents

Advertisement

TROUBLESHOOTING CONTINUED
Error Codes
NOTE: Error codes appear on the In Service display.
Error
Error Type
Code
0
Cam Sense
Error
1
Cycle Step
Error
2
Regen
Failure
3
Memory
Error
UD
Upper Drive
Sync
Cause
The valve drive took longer
than 6 minutes to advance to
the next regeneration position
The control experienced an
unexpected cycle input
The system has not
regenerated for more than 99
days (or 7 days if the Control
Type has been set to Day-of-
Week)
Control board memory failure
Power failure install
programming change
Reset and Recovery
Unplug the unit and examine the powerhead. Verify that all cam
switches are connected to the circuit board and functioning
properly. Verify that the motor and drive train components are in
good condition and assembled properly. Check the valve and verify
that the piston travels freely. Replace/reassemble the various
components as necessary.
Plug the unit back in and observe its behavior. The unit should
cycle to the next valve position and stop. If the error re-occurs,
unplug the unit and contact technical support.
Unplug the unit and examine the powerhead. Verify that all cam
switches are connected to the circuit board and functioning
properly. Enter Master Programming mode and verify that the
valve type and system type are set correctly with regard to the
unit itself.
Step the unit through a manual regeneration and verify that it
functions correctly. If the error re-occurs unplug the unit and
contact technical support.
Perform a Manual Regeneration to reset the error code.
If the system is metered, verify that it is measuring flow by
running service water and watching for the flow indicator on the
display. If the unit does not measure flow, verify that the meter
cable is connected properly and that the meter is
functioning properly.
Enter a Master Programming Mode and verify that the unit is
configured properly. As appropriate for the valve configuration,
check that the correct system capacity has been selected, that the
day override is set properly, and that meter is identified correctly.
If the unit is configured as a Day-of-Week system, verify that at
least one day is set ON. Correct the settings as necessary.
Perform a Master Reset and reconfigure the system via Master
Programming Mode. After reconfiguring the system, step the valve
through a manual regeneration. If the error re-occurs unplug the
unit and contact technical support.
Valve will automatically recover.
FLECK
5600SXT Downflow Service Manual
• 21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents