Solar Input Configuration - Latronics PV Edge Grid 915-GI-72 User Manual

Interactive inverter
Table of Contents

Advertisement

Panel Power
at 25°C
50W
55W
60W
65W
70W
75W
80W
85W
90W
95W
100W
110W
120W
120W
125W
130W
140W
150W
160W
165W
170W
175W
Note 1: The DC input is suitable for connection to solar modules only.
Note 2: Recommended Solar Input 1500W Absolute Maximum 1575W.
Note 3: Solar input must be configured for strings of 6x12V or 3x24V modules.
Note 4: Ensure that all solar modules are of the same type and brand to ensure the maximum power point and
voltage variation with temperature are consistent for all modules which will ensure maximum system output.
Note 5: Do not use different wattage modules in the same string, as the power is limited to the module of the
lowest rating. Eg. A string consisting of 1x50W and 5x100W modules will produce the same power output as
6x50W modules.
Note 6: Different wattage solar modules can be used in separate strings if all modules are of the same brand
and type in each string . Eg. 1 string of 6x75W (450W) plus another string of 6x75W (450W) plus a string of
6x100W (600W) would be acceptable and give a total of 1500W.
LATRONIC SUNPOWER PTY LTD

SOLAR INPUT CONFIGURATION

Module
Number of
Type
Panels Per
String
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
12V
6
24V
3
12V
6
24V
3
24V
3
24V
3
24V
3
24V
3
24V
3
24V
3
Doc. No: M61
Number of
Strings
5
4
4
4
3
3
3
3
2
2
2
2
2
4
2
4
3
3
3
3
3
3
www.latronics.com.au
Solar Input Power
1500W
1320W
1440W
1560W
1260W
1350W
1440W
1530W
1080W
1140W
1200W
1320W
1440W
1440W
1500W
1560W
1260W
1350W
1440W
1485W
1530W
1575W
Page 4