Lanning Of The Ductwork; Nstalling The Uctwork And; R Egisters - Venmar 41502 Installation Manual

Avs units constructo 1.0 hrv and constructo 1.0 erv
Hide thumbs Also See for 41502:
Table of Contents

Advertisement

2.
INSTALLATION (
2.5
P
D
LANNING OF THE
UCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of insulated ducts to a minimum.
• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would
cause clogging of the filters and recovery module.
• If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
2.6
I
D
NSTALLING THE
UCTWORK AND
Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas furnace, a gas
water heater or a fireplace.
2.6.1 F
D
S
ULLY
UCTED
Stale air exhaust ductwork:
• Install the stale air exhaust registers where the contaminants are produced: Kitchen, living room, etc. Position the registers as far
from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.
• If a register is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.
• Install the registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.
Fresh air distribution ductwork:
• Install the fresh air distribution registers in bedrooms, dining rooms, living room and basement.
• Keep in mind that the fresh air registers must be located as far as possible from the stale air registers.
• Install the registers in the ceiling OR 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall. The duct length should be
at least 15' (4.6 m). (The fresh air will then flow through the room and mix with room air, ensuring a continuous renewed airflow.)
• If a register must be floor installed, direct the airflow up the wall.
2.6.2 C
D
P
ENTRAL
RAW
Stale air exhaust ductwork:
Same as for Fully Ducted System, described on point 2.6.1
Fresh air distribution ductwork:
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety
regulations. Please refer to your local building code.
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow
produced by the HRV/ERV. Also, use a steel duct.
There are 2 methods for connecting the unit to the furnace/air handler:
Method 1: Supply side connection
• Cut an opening into the furnace supply duct at least 18 inches (0.5 m) from the
furnace/air handler.
• Connect this opening to the Fresh air to building port of the HRV/ERV (use steel
duct, see figure at right).
• Make sure the HRV/ERV duct forms an elbow inside the furnace/air handler ductwork.
• If desired, interlock (synchronize) the furnace/air handler blower operation (see
Section 4).
Method 2: Return side connection
• Cut an opening into the furnace return duct not less than 10 feet (3.1 m) from the
furnace/air handler (A+B).
• Connect this opening to the Fresh air to building port of the HRV/ERV(see figure at right).
NOTE: For Method 2, it is not essential that the furnace/air handler runs when the unit is in
operation, but we recommend it. If desired, interlock (synchronize) the furnace/air
handler blower operation (see Section 4).
'
)
CONT
D
R
EGISTERS
(
S
YSTEM
AS ILLUSTRATED IN
ECTION
S
(
OINT
YSTEM
AS ILLUSTRATED IN
!
WARNING
1.1)
S
1.2)
ECTION
!
WARNING
CAUTION
7
S
TEEL DUCT
VJ0036
A+B=
VJ0035
10' (3.1
THAN
M
18"
INIMUM
(0.5
)
M
A
B
NOT LESS
)
M

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

415004150641504

Table of Contents